EN
PART 2. INSTALLATION MANUAL
Note on Residual current operated circuit-breakers
If connecting power to fixed wiring, an all-pole disconnection device which has at least 3mm clearances in all poles,
and have a leakage current that may exceed 10mA, the residual current operated circuit-breakers with integral
overcurrent protection having a rated residual operating current not exceeding 30mA, and disconnection must be
incorporated in the fixed wiring in accordance with the wiring rules.
NOTE:
The cographs are for explanation purpose only. Your machine may be slightly dierent. The actual shape shall
prevail.
Air Residual current operated
circuit-breakers
Outdoor unit power wires
Indoor&Oudoor connective wires
(purchased separately)
Indoor unit power wires
Outdoor unit
Indoor unit
(purchased separately)
(purchased separately)
Air Residual current operated
circuit-breakers
WARNING
Before performing any electrical or wiring work, turn off the main power to the system.
7.1. Outdoor Unit Wiring
1. Prepare the cable for connection
a. You must first choose the right cable size. Be sure to use H07RN-F cables.
Rated Current of Appliance (A)
Nominal Cross-Sectional Area (mm
2
)
> 3 and ≤ 6
0.75
> 6 and ≤ 10
1
> 10 and ≤ 16
1.5
> 16 and ≤ 25
2.5
> 25 and ≤ 32
4
> 32 and ≤ 40
6
Minimum Cross-Sectional Area of Power and Signal Cables (For reference)