Hazardous Area Oxymitter 5000
8-6
Instruction Manual
IM-106-350C, Rev 2.2
July 2008
Table 8-1. Diagnostic/Unit
Alarm Fault Definitions -
Membrane Keypad Only
*Critical alarm conditions will render the O
2
measurement as unusable. Alarms which are not self-clearing (Self-Clearing = NO) will require
a reset. Perform the Reset Procedure in Section 3: Configuration of Oxymitter 5000 with Membrane Keypad to continue operation.
**The CALIBRATION RECOMMENDED alarm flashes the Calibration Recommended LED on the operator's keypad.
Table 8-2. Diagnostic/Unit
Alarm Fault Definitions - LOI
LED
Flashes
Status
Fault Number
Recoverable
HEATER T/C
1
2
3
4
Open
Shorted
Reversed
A/D Comm Error
1
2
3
4
No
No
No
No
HEATER
1
2
3
4
5
Open
High High Temp
High Case Temp
Low Temp
High Temp
5
6
7
8
9
No
No
Yes
Yes
Yes
O
2
CELL
1
3
4
High mV
Bad
EEprom Corrupt
10
11
12
Yes
Yes
No
CALIBRATION
1
2
3
**
Invalid Slope
Invalid Constant
Last Calibration Failed
Calibration Recommended
13
14
15
Yes
Yes
Yes
Yes
Message
Status
Fault Number
Self Clearing
O2 T/C OPEN
Heater T/C Open
1
No
O2 T/C SHORTED
Heater T/C Shorted
2
No
O2 T/C REVERSED
Heater T/C Polarity Reversed
3
No
ADC ERROR
A/D Comm Error
4
No
O2 HEATER OPEN
O2 Heater Open
5
No
VERY HI O2 TEMP
Very High Process Temperature
6
No
BOARD TEMP HI
Electronics Overheated
7
Yes
O2 TEMP LOW
Low Process Temperature
8
Yes
O2 TEMP HI
High Process Temperature
9
Yes
O2 CELL OPEN
O2 Cell Open
10
Yes
O2 CELL BAD
O2 Cell Failed
11, 13, 14
Yes
EEPROM CORRUPT
EEprom Failed
12
No
CALIB FAILED
Last Calibration Failed
15
Yes
LINE FREQ ERROR
Incorrect Input Line Frequency Detected on Power Up
No
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 14: ...Hazardous Area Oxymitter 5000 iv Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 82: ...Hazardous Area Oxymitter 5000 7 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 130: ...Hazardous Area Oxymitter 5000 9 24 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 140: ...Hazardous Area Oxymitter 5000 11 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 172: ...Hazardous Area Oxymitter 5000 B 2 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 192: ...Hazardous Area Oxymitter 5000 D 14 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 210: ...Hazardous Area Oxymitter 5000 E 18 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 212: ...Instruction Manual IM 106 350C Rev 2 2 July 2008 Hazardous Area Oxymitter 5000 Index 2 ...