![Rosemount Oxymitter 5000 Instruction Manual Download Page 87](http://html1.mh-extra.com/html/rosemount/oxymitter-5000/oxymitter-5000_instruction-manual_1487464087.webp)
Instruction Manual
IM-106-350C, Rev 2.2
July 2008
8-5
Hazardous Area Oxymitter 5000
SPS 4001B and IMPS 4000, 1-4 probes
• One contact closure per probe from the control room to the SPS 4001B
or IMPS 4000 for "calibration initiate".
• One contact output per probe from the SPS 4001B or IMPS 4000 to the
control room for "in calibration" notification.
• One contact output per probe from the SPS 4001B or IMPS 4000 to the
control room for "calibration failed" notification. (Includes output from
pressure switch indicating "cal gas bottles empty").
Additional IMPS 4000 Alarm Contacts
• One contact per IMPS 4000 for "low calibration gas flowing".
• One contact per IMPS 4000 for "high calibration gas flowing".
IDENTIFYING AND
CORRECTING ALARM
INDICATIONS
For a Hazardous Area Oxymitter 5000 with a membrane keypad, faults are
indicated by four diagnostic, or unit, alarm LEDs. A pattern of repeating blinks
define the problem. A condensed table of the errors and the corresponding
blink codes can be found on the inside right cover of the electronics housing.
Table 8-1 also identifies the blink code and fault status of each LED.
For a Hazardous Area Oxymitter 5000 with the optional LOI, alarm messages
are displayed on the LOI display window when the alarm status display is
accessed via the LOI menu. A listing of the alarm/fault messages and the
related fault status descriptions and fault numbers are shown in Table 8-2.
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 14: ...Hazardous Area Oxymitter 5000 iv Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 82: ...Hazardous Area Oxymitter 5000 7 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 130: ...Hazardous Area Oxymitter 5000 9 24 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 140: ...Hazardous Area Oxymitter 5000 11 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 172: ...Hazardous Area Oxymitter 5000 B 2 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 192: ...Hazardous Area Oxymitter 5000 D 14 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 210: ...Hazardous Area Oxymitter 5000 E 18 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 212: ...Instruction Manual IM 106 350C Rev 2 2 July 2008 Hazardous Area Oxymitter 5000 Index 2 ...