![Rosemount Oxymitter 5000 Instruction Manual Download Page 205](http://html1.mh-extra.com/html/rosemount/oxymitter-5000/oxymitter-5000_instruction-manual_1487464205.webp)
Instruction Manual
IM-106-350C, Rev 2.2
July 2008
E-13
Hazardous Area Oxymitter 5000
Figure E-6. PID Function Block
Diagram for Feedfoward Control
Cascade Control with
Master and Slave Loops
Situation
A slave loop is added to a basic PID control configuration to measure and
control steam flow to the steam heater. Variations in the steam pressure
cause the temperature in the heat exchanger to change. The temperature
variation will later be sensed by TT101. The temperature controller will modify
the valve position to compensate for the steam pressure change. The process
is slow and causes variations in the product temperature. Figure E-7
illustrates the process instrumentation diagram.
Figure E-7. PID Function Block
Cascade Control Example
Outlet
Temperature
Input
Inlet
Temperature
Input
BKCAL_IN
BKCAL_OUT
OUT
OUT
OUTOUT
IN
CAS_IN
FF_VAL
AI
Function
Block
AI
Function
Block
PID
Function
Block
AO
Function
Block
TT101
TC101
TCV101
TT100
38740098
38740099
Steam
Supply
FC
101
Steam Heater
Condensate
TC
101
TT
101
FT
101
TT
100
TCV
101
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 14: ...Hazardous Area Oxymitter 5000 iv Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 82: ...Hazardous Area Oxymitter 5000 7 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 130: ...Hazardous Area Oxymitter 5000 9 24 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 140: ...Hazardous Area Oxymitter 5000 11 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 172: ...Hazardous Area Oxymitter 5000 B 2 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 192: ...Hazardous Area Oxymitter 5000 D 14 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 210: ...Hazardous Area Oxymitter 5000 E 18 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 212: ...Instruction Manual IM 106 350C Rev 2 2 July 2008 Hazardous Area Oxymitter 5000 Index 2 ...