E-17
Hazardous Area Oxymitter 5000
Mode sheds
from RCAS to
AUTO
1. Remote Cascade Value
2. Shed Timer
1. Host system is not writing RCAS_IN with a
quality and status of “good cascade” within shed
time (see 2 below).
2. The mode shed timer, SHED_RCAS in the
resource block is set too low. Increase the value.
Mode sheds
from ROUT to
MAN
1. Remote output value
2. Shed timer
1. Host system is not writing ROUT_IN with a
quality and status of “good cascade” within shed
time (see 2 below).
2. The mode shed timer, SHED_RCAS, in the
resource block is set too low. Increase the value.
Process and/or
block alarms
will not work
1. Features
2. Notification
3. Status Options
1. FEATURES_SEL does not have Alerts
enabled. Enable the Alerts bit.
2. LIM_NOTIFY is not high enough. Set equal to
MAX_NOTIFY.
3. STATUS_OPTS has Propagate Fault Forward
bit set. This should be cleared to cause an alarm
to occur.
Symptom
Possible Causes
Corrective Action
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 14: ...Hazardous Area Oxymitter 5000 iv Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 82: ...Hazardous Area Oxymitter 5000 7 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 130: ...Hazardous Area Oxymitter 5000 9 24 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 140: ...Hazardous Area Oxymitter 5000 11 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 172: ...Hazardous Area Oxymitter 5000 B 2 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 192: ...Hazardous Area Oxymitter 5000 D 14 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 210: ...Hazardous Area Oxymitter 5000 E 18 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 212: ...Instruction Manual IM 106 350C Rev 2 2 July 2008 Hazardous Area Oxymitter 5000 Index 2 ...