Hazardous Area Oxymitter 5000
E-16
Instruction Manual
IM-106-350C, Rev 2.2
July 2008
TROUBLESHOOTING
Refer to Table E-3 to troubleshoot any problems that you encounter.
Table E-3. Troubleshooting
Symptom
Possible Causes
Corrective Action
Mode will not
leave OOS
1. Target mode not set
2. Configuration error
3. Resource block
4. Schedule
1. Set target mode to something other than OOS.
2. BLOCK_ERR will show the configuration error
bit set. The following are parameters that must be
set before the block is allowed out of OOS:
a. BYPASS must be off or on and cannot be left
at initial value of 0.
b. OUT_HI_LIM must be less than or equal to
OUT_LO_LIM.
c. SP_HI_LIM must be less than or equal to
SP_LO_LIM.
3. The actual mode of the Resource block is
OOS. See Resource Block Diagnostics for
corrective action.
4. Block is not scheduled and therefore cannot
execute to go to Target Mode. Schedule the block
to execute.
Mode will not
leave IMAN
1. Back Calculation
1. BKCAL_IN
a. The link is not configured (the status would
show “Not Connected”).Configure the
BKCAL_IN link to the downstream block.
b. The downstream block is sending back a
Quality of “Bad” or a Status of “Not Invited”.
See the appropriate downstream block
diagnostics for corrective action.
Mode will not
change to
AUTO
1. Target mode not set
2. Input
1. Set target mode to something other than OOS.
2. IN
a. The link is not configured (the status would
show “Not Connected”). Configure the IN link
to the block.
b. The upstream block is sending back a
Quality of “Bad” or a Status of “Not Invited”.
See the appropriate upstream block
diagnostics for corrective action.
Mode will not
change to CAS
1. Target mode not set
2. Cascade Input
1. Set target mode to something other than OOS.
2.CAS_IN
a. The link is not configured (the status would
show “Not Connected”). Configure the
CAS_IN link to the block.
b. The upstream block is sending back a
Quality of “Bad” or a Status of “Not Invited”.
See the appropriate up stream block
diagnostics for corrective action.
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 14: ...Hazardous Area Oxymitter 5000 iv Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 82: ...Hazardous Area Oxymitter 5000 7 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 130: ...Hazardous Area Oxymitter 5000 9 24 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 140: ...Hazardous Area Oxymitter 5000 11 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 172: ...Hazardous Area Oxymitter 5000 B 2 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 192: ...Hazardous Area Oxymitter 5000 D 14 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 210: ...Hazardous Area Oxymitter 5000 E 18 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Page 212: ...Instruction Manual IM 106 350C Rev 2 2 July 2008 Hazardous Area Oxymitter 5000 Index 2 ...