Chapter 3 Operation/Setup
Accura 3300E User Guide
Page 48
ⓒ
2015 Rootech Inc. All Rights Reserved
METER Setup
Connection[
Conn
→
Connection
]
Setup Range
-
3P4U[3 Phase 4 Wire, default]
3 phase 4 wire
-
3P3U[3 Phase 3 Wire]
3 phase 3 wire
-
1P3U[Single Phase 3 Wire]
Single phase 3 wire
-
1P2U[Single Phase 2 Wire]
Single phase 2 wire
PT Rating[
Pt
→
PT
]
Ratio of primary and secondary line to line voltage ratio is used as conversion ratio for primary
voltage. Primary and secondary line to line voltage for each connection method are followed. In
case of direct connection without using PT, primary and secondary line to line voltage should be
equally configured.
Setup Range
-
Pr[Primary]
PT primary line to line voltage rating
[d][d][d][d][d][d]
1
000001 - 999999
[default 380]
-
Sc[Secondary]
PT secondary line to line voltage rating
[d][d][d]
001 - 999
[default 380]
1
d
→
decimal number