Accura 3300E User Guide
Chapter 3 Operation/Setup
ⓒ
2015 Rootech Inc. All Rights Reserved
Page 55
Event Setup
Fuse fail Event[
FuSE FaIL
→
Fuse Fail
]
In case that a phase voltage is measured as 0 and the corresponding phase current is measured
as non-zero value, it is detected as fuse fail event.
Setup Range
-
On
Fuse Fail event on
-
oFF[default]
Fuse Fail event off
Phase Open & Blackout Event[bLak Out
→
Blackout]
In case that both voltage and current of a phase are measured as 0, it is detected as phase open
event. In case that voltage and current of all phase are measured as 0, it is detected as blackout
event.
Setup Range
-
On
Phase open and Blackout event on
-
oFF[default]
Phase open and Blackout event off