Chapter 3 Operation/Setup
Accura 3300E User Guide
Page 54
ⓒ
2015 Rootech Inc. All Rights Reserved
Voltage Phase Selection [SELEt
→
Select
]
Setup Range
-
A [d]
1
B [d]
C [d]
[default 123]
The wiring sequence of voltage
phases: 123 indicates A, B, and
C phases are connected to the
V1, V2, and V3 voltage input
ports, respectively.
-
P[Positive, default]
Normal voltage wiring
-
N[Negative]
Reverse voltage wiring
1
d
→
decimal number
Current Phase Selection [SELEt
→
Select
]
Setup Range
-
A [d]
1
B [d]
C [d]
[default 123]
The wiring sequence of current
phases: 123 indicates A, B, and
C phases are connected to the
current input ports, 1, 2, and 3,
respectively.
-
P[Positive, default]
Normal current flow from the
Source(S) to the Load(L)
-
n[Negative]
Reverse current flow from the
Load(L) to the Source(S)
1
d
→
decimal number