Accura 3300E User Guide
APPENDIX C Accuracy/Reliability
ⓒ
2015 Rootech Inc. All Rights Reserved
Page 85
Appendix C Accuracy/Reliability
Accuracy
Parameter
Display Range
Accuracy
Line to neutral Voltage
0.0
–
9999 V, kV
±
0.2% Reading
Line to line voltage
0.0
–
9999 V, kV
±
0.2% Reading
Current
0.000
–
9999 A, kA
±
0.2% Reading
Power
Active
0.000 -
±
9999 kW, MW
5
Class 0.5S
1
Reactive
0.000 -
±
9999 kVar, MVar
5
Class 0.5S
2
Apparent
0.000 - 9999 kVA, MVA
5
Class 0.5
3
Energy
Active
0 -
±
999,999,999 kWh
Class 0.5S
1
Reactive
0 -
±
999,999,999 kVarh
Class 0.5S
2
Apparent
0 - 999,999,999 kVAh
Class 0.5
3
Demand
Power
0.000 -
±
9999 kW, MW
Class 0.5S
1
Current
0.000 - 9999 A, kA
±
0.2% Reading
Frequency
42
–
69 Hz
±
10 mHz
Power factor
0.000 - 1.000 LEAD/LAG
±
0.5% Full scale
THD
Voltage
0.0 - 999.9%
±
0.5% Full scale
Current
0.0 - 999.9%
±
0.5% Full scale
TDD
Current
0.0 - 999.9%
±
0.5% Full scale
Crest factor
4
0.0 - 999.9
±
0.5% Full scale
K-factor
4
0.0 - 999.9
±
0.5% Full scale
1
Class 0.5S means IEC 62053-22 Class 0.5S.
2
Class 0.5S means IEC 62053-24 Class 0.5S.
3
Class 0.5 means IEC 61557-12 Class 0.5.
4
The data are not displayed on the LCD screen of Accura 3300E and are provided only by communication.
5
The LCD screen of Accura 3300E displays x1000 kW/kVar/kVA values.
Power Quality
Item
Compliance
Condition
Accuracy
Voltage/Current
THD
1
-
Up to the 31st order ± 0.5% Full scale
Current TDD
2
-
Up to the 31st order ± 0.5% Full scale
Summary of Contents for ACCURA 3300E