SLC 500 SYSTEMS

SELECTION GUIDE

BULLETIN 1746 AND 1747

www.aotewell.com

www.fa-market.com

[email protected]

AoteWell International.inc

[email protected]

Tel: +852-6563-2160

Summary of Contents for SLC 500 Thermocouple

Page 1: ...SLC 500 SYSTEMS SELECTION GUIDE BULLETIN 1746 AND 1747 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 2: ...board Ethernet DH or DH 485 as well as options for ControlNet DeviceNet or Remote I O communications Broad selection of I O Select from over 60 modules to control discrete analog and temperature signals Third party specialty modules are also available from Encompass partners to customize control solutions for your application needs Industrially hardened product Designed to withstand the vibrations...

Page 3: ...pment time and maximize productivity Typical Systems With up to 64 K of configurable data program memory available and over 60 types of I O modules as well as a choice of networking options the SLC system provides a powerful solution for stand alone or distributed industrial control Table of Contents See Selecting SLC 500 I O Modules page 8 Selecting Network Communications page 39 Selecting an SLC...

Page 4: ...cal chassis together with chassis interconnect cables to extend the backplane signal lines from one chassis to another Power Supply Processor I O Modules Power Supply I O Modules I O Modules Chassis Interconnect Cable Chassis Interconnect Cable Power Supply Distributed Systems More complex systems can use distributed I O multiple controllers joined across networks I O in multiple platforms that ar...

Page 5: ...ork configurations and the placement of components in each location Decide at this time whether each chassis will have it s own controller or a networked solution SLC 500 processors are available with a large range of memory sizes 1 K through 64 K and can control up to 4096 input and 4096 output signals All modular processors except the SLC 5 01 processor are capable of controlling remotely locate...

Page 6: ...rts for communication with other processors computers and remotely located I O Each processor has one or two built in ports for either EtherNet IP DH DH 485 or RS 232 DF1 ASCII or DH 485 protocol communication In addition to the on board ports available with SLC processors you have the option of providing another communication port for an SLC processor by adding a communication module Adapter modu...

Page 7: ...0 C 32 140 F Storage 40 85 C 40 185 F Humidity 5 95 without condensation Vibration Operating 1 0 g at 5 2000 Hz Non operating 2 5 g at 5 2000 Hz Shock Operating 30 g 3 pulses 11 ms for all modules except relay contact Operating 10 g 3 pulses 11 ms for relay contact modules 1746 OWx and 1746 IOx combo Non operating 50 g 3 pulses 11 ms Free fall drop test Portable 2 268 kg 5 lb or less at 0 762 m 30...

Page 8: ... plates that accept two 14 AWG 2 mm2 wires LED indicators on the front of each module display the status of each I O point 32 channel I O modules are equipped with a 40 pin MIL C 83503 type header and a removable wiring connector 1746 N3 The connector can be assembled with the wire type and length of your choice Output modules are available with solid state AC solid state DC and relay contact type...

Page 9: ... dc 16 Current Sinking DC Output Module 1746 OV32 24V dc 32 Current Sinking DC Output Module 1746 OVP16 24V dc 16 High Current Sinking DC Output Module 1746 OG16 5V dc 16 Current Sinking TTL Output Module AC Modules 1746 IA4 100 120V ac 4 120V ac Input Module page 12 AC Input Modules 1746 IA8 100 120V ac 8 120V ac Input Module 1746 IA16 100 120V ac 16 120V ac Input Module 1746 IM4 200 240V ac 4 24...

Page 10: ...is connected in parallel with an inductive load use surge suppression across the load to protect the input module from damage caused by reverse voltage Refer to the SLC 500 Modular Hardware Style User Manual publication 1747 UM011 for more information on surge suppression Specifications Number of Inputs Points Per Common Voltage Category Operating Voltage Range Backplane Current mA at 5V Backplane...

Page 11: ... once every 2 s 60 C 140 F Surge current 32 A per module for 10 ms Specifications Number of Outputs Points Per Common Voltage Category Operating Voltage Range Backplane Current mA at 5V Backplane Current mA at 24V Voltage Drop On State Output Max Load Current Min Leakage Current Off State Output Max Signal On Delay Max resistive load Signal Off Delay Max resistive load Continuous Current per Modul...

Page 12: ...ing Voltage Range 85 265V ac 47 63 Hz Backplane Current mA at 5V 185 mA 370 mA Backplane Current mA at 24V 0 mA 0 mA 0 mA Voltage Drop On State Output Max 1 50V 1 0 A 1 50V 0 50 A 1 2V 2 0 A Load Current Min 10 mA 10 mA 10 mA Leakage Current Off State Output Max 2 mA 2 mA 2 mA Surge Current per Point max 10 0 A for 25 ms 17 0 A for 25 ms Signal On Delay Max resistive load 1 ms 1 ms 1 ms Signal Off...

Page 13: ... 2 A The continuous current per module must be limited so the module power does not exceed 1440 VA Relay Output Modules Specifications 1746 OW4 1746 OW8 1746 OW16 1746 OX8 Number of Outputs 4 8 16 8 Points Per Common 4 4 8 individually isolated Voltage Category ac dc Relay Operating Voltage Range 5 125V dc 5 265V ac Backplane Current mA at 5V 45 mA 85 mA 170 mA 85 mA Backplane Current mA at 24V 45...

Page 14: ... 500 1746 Analog I O Modules Analog I O modules feature user selectable voltage or current inputs backplane isolation removable terminal blocks and diagnostic feedback The 1746 NI4 1746 NIO4I and 1746 NIO4V input channels are filtered to reject high frequency noise and provide 14 to 16 bit range dependent resolution All 4 channel analog output modules provide 14 bit resolution and a 2 5 ms convers...

Page 15: ... Specifications page 17 Output Specifications 1746 NIO4V High Resolution 2 Analog Input 2 Analog Voltage Output Module 20 20 mA or 10 10V dc Inputs 10 10V dc Outputs page 16 General Input Specifications page 17 Voltage Input Specifications page 17 Output Specifications 1746 FIO4I 2 Fast Analog Input 2 Analog Current Output Module 0 20 mA or 0 10V dc Inputs 0 20 mA Outputs page 16 General Input Spe...

Page 16: ... Input Range Current Input Coding Absolute Maximum Input Voltage Input Impedance Resolution Overall Accuracy at 25 C 77 F Overall Accuracy 0 60 C 32 140 F Overall Accuracy Drift Gain Error at 25 C 77 F Gain Error 0 60 C 32 140 F Gain Error Drift Current Loop Input Specifications for 4 Channel Modules 1746 NI4 1746 NIO4I 1746 NIO4V 1746 FIO4I 1746 FIO4V 20 mA 20 mA 20 mA 20 mA 20 mA 20 mA nominal 3...

Page 17: ...all Accuracy 0 60 C 32 140 F Overall Accuracy Drift maximum Gain Error at 25 C 77 F Gain Error 0 60 C 32 140 F Gain Error Drift maximum Output Specifications for 4 Channel Modules 1746 FIO4I 1746 NIO4I 1746 NO4I 1746 FIO4V 1746 NIO4V 1746 NO4V 2 2 4 2 2 4 55 mA 55 mA 55 mA 55 mA 55 mA 55 mA 150 mA 145 mA 195 mA 120 mA 115 mA 145 mA Tested at 500V ac and 710V dc for 60 seconds 21 mA 10V dc 0 20 mA ...

Page 18: ...gle ended configuration Tested at 500V ac and 710V dc for 60 seconds 0 75 ms per enabled channel 101 107 ms maximum 1 7 ms maximum 101 107 ms maximum module performs continuous autocalibration Input Step Response for 1746 NI8 Filter Frequency Step Response for 1746 NI8 1 Accuracy 0 1 Accuracy 0 05 Accuracy 1 Hz 730 ms module update time 1100 ms module update time 1200 ms module update time 2 Hz 36...

Page 19: ... F 0 05 maximum Gain Error Drift 12 ppm C Overvoltage Capability 7 5V ac RMS maximum Voltage Input Specifications for 1746 NI8 Cat No 1746 NI8 Voltage Input maximum 30V between any two signal terminals Input Impedance 1M Ω Input Resolution 1 mV Display Resolution 1 mV Overall Module Accuracy 0 60 C 32 140 F 0 1 Overall Module Accuracy Drift 17 ppm C Gain Error at 25 C 77 F 0 05 maximum Gain Error ...

Page 20: ...t 5V 120 mA 120 mA Backplane Current mA at 24V 250 mA 160 mA Backplane Power Consumption 5 6 W 5 6 W Thermal Dissipation Max 6 6 W 4 44 W Isolation Voltage Tested at 500V dc Tested at 500V dc Number of Outputs 8 8 Output Type Current Voltage Output Range 0 21 5 mA 10 25V dc Output Coding proportional scaling 0 32 767 32 768 32 767 Resolution 16 bit 366 nA count 16 bit 320 μV count Non Linearity DA...

Page 21: ...V maximum between any two signal terminals 10 25V relative to the analog common terminal 20 5V maximum between any two signal terminals 6 Hz 10 Hz 20 Hz 40 Hz 60 Hz 80 Hz 100 Hz 250 Hz 6 Hz 10 Hz 20 Hz 40 Hz 60 Hz 80 Hz 100 Hz 250 Hz 0 20 mA 20 mA 4 20 mA 0 1 mA 10V dc 0 5V dc 1 5V dc 0 10V dc Engineering Units Scaled for PID Proportional Counts 32 768 32 767 range Proportional Counts User Defined...

Page 22: ... 80 Hz 54 ms 39 ms 26 ms 4 ms 100 Hz 37 ms 27 ms 18 ms 4 ms 250 Hz 18 ms 13 ms 9 ms 4 ms Temperature Modules SLC 500 Thermocouple mV Input Modules All modules interface to thermocouple types J K T E R S B and N and also accept millivolt signals that standard analog modules are not able to detect The 1746 INT4 module also interfaces with thermocouple types C and D All modules provide fully integrat...

Page 23: ...adder program once a year as required Isolation 500V dc transient between inputs and chassis ground and between inputs and backplane 2V dc continuous between channels series B or later 500V dc transient between inputs and chassis ground and between inputs and backplane 12 5V dc continuous between channels 1000V dc transient or 150V ac continuous channel to channel or channel to backplane The modul...

Page 24: ... 83 C 6 90 F C 0 2317 C 32 4201 F N A N A 2 38 C 4 11 F D 0 2317 C 32 4201 F N A N A 2 52 C 4 54 F CJC Sensor 0 85 C 32 185 F N A N A N A Thermocouple type only available with 1746 INT4 module DC Millivolt Input Ranges for 1746 NT4 1746 NT8 and 1746 INT4 Modules Input Type Range Accuracy at 25 C 77 F 50 mV 50 mV dc 50 mV dc 50 μV 100 mV 100 mV dc 100 mV dc 50 μV RTD Input Modules The RTD modules i...

Page 25: ...n a channel is enabled Autocalibration at power up and user enabled periodic calibration Isolation Voltage Channel to Channel None 5V Isolation Voltage Input to Backplane 500V ac for 1 minute Common Mode Voltage Separation 1V maximum Cannot use for 10 Ω Copper RTD Recommended for use with higher resistance ranges for both RTDs and direct response inputs 1000 Ω RTDs and 3000 Ω resistance input Cont...

Page 26: ...r 200 Ω platinum RTDs with 0 5 excitation current depends on the following criteria 1 Module accuracy is 0 6 C after you apply power to the module or perform an autocalibration at 25 C 77 F ambient with the module operating temperature at 25 C 77 F 2 Module accuracy is 0 6 C DT x 0 034 C C after you apply power to the module or perform an autocalibration at 25 C 77 F ambient with the module operat...

Page 27: ... actively counting pulses The Z gate input channel can be used for storing holding and resetting counter data High Speed Counter Specifications Cat No 1746 HSCE 1746 HSCE2 Number of Inputs 1 set A B Z differential or single ended inputs 5V dc 12V dc or 24V dc 2 sets A B Z 2 quadrature encoders or 4 pulse differential or single ended inputs Input Voltage Range differential 0 5V dc single ended 5V d...

Page 28: ...log Inputs Analog Output Digital Input Digital Output Excitation Output Cat No 1746 BLM Backplane Current mA at 5V 110 mA Resolution 14 bits Isolation Voltage Tested at 500V dc for 60 s Conversion Rate 10 kHz Number of Inputs 4 Digital 4 Analog Number of Outputs 4 Digital 4 Analog 1 Excitation Differential Input Range 10V dc Common Mode Input Range 200V dc Differential Impedance 800 kΩ Common Mode...

Page 29: ...Hz 60 dB 60 Hz Common Mode Rejection 120 dB 50 60 Hz with 1 kΩ imbalance Channel Bandwidth 3dB 8 Hz Resolution 16 bit resolution or 15 bit plus sign Data Format 16 bit signed integer natural binary Backplane Current mA at 5V 110 mA Backplane Current mA at 24V 85 mA Isolation Voltage Tested at 1000V ac for 60 s Motion Control Modules Stepper Control Module The 1746 HSTP1 is a single axis stepper co...

Page 30: ...quency Max 300 kHz 0 quadrature error Outputs 1 general purpose local fast output Module Update Time 2 ms Positioning Modules Open Loop Velocity This module provides an ideal control strategy for simple hydraulic applications It can accelerate and decelerate the hydraulic ram using as many as seven extend and seven retract segments Compatible LDTs are Balluff BTL 2 L2 or M2 Gemco Quick Stick II Sa...

Page 31: ...1492 AIFMQS interface module is required for CE certification 1746 QS Specifications Cat No 1746 QS Number of Inputs 4 Number of Outputs 4 Backplane Current mA at 5V 1000 mA Backplane Current mA at 24V 200 mA Voltage Category Input LDT with RPM or DPM Output 10V dc 10V dc Analog Output 10 10V dc at 5 mA Output Resolution 12 bit Module Update Time 2 ms Fail safe Timers Drive Output Disable 15 μs So...

Page 32: ...ule is connected to any device e g DTAM either directly or through a 1747 AIC Link Coupler add the appropriate current loading for the device to the BASIC module s power supply loading value at 24V dc 24 Kbytes battery backed RAM 0 150 0 040 RS 232 423 RS 422 RS 485 RS 232 423 RS 422 RS 485 DH 485 710V dc for 1 minute 710V dc for 1 minute 710V dc for 1 minute 15 m 50 ft 1230 m 4000 ft 920 m 3000 f...

Page 33: ...IC Development Software an optional DOS based software package provides a structured and efficient means to create and debug BASIC programs It uses the personal computer to facilitate editing compiling uploading and downloading of BASIC programs The PC requires 640 Kbytes of RAM a fixed disk drive with 2 Mbytes of free disk space and DOS version 3 1 or later Bulletin 1492 Wiring Options Wiring sys...

Page 34: ...B B B B 120V AC LEDs and extra terminals for outputs 1492 IFM20D120 2 C D 120V AC LEDs and extra terminals for inputs 1492 IFM20D120A 2 A 3 wire sensor with 24V AC DC LEDs 1492 IFM20D24 3 B B B B B 8 Individually isolated with 24 48V AC DC LEDs and 4 terminals output 1492 IFM20DS24 4 S 8 Individually isolated with 120V AC LEDs and 4 terminals output 1492 IFM20DS120 4 S 240V AC LEDs and extra termi...

Page 35: ...4 point isolated groups with four terminals input and 120V AC DC blown fuse indicators 1492 IFM20F FS120A 4 8 Individually isolated with 4 terminals output and 240V AC DC blown fuse LED indicators 1492 IFM20F FS240 4 S Relay Master and Expander 20 Terminal XIMs Description Cat No I O Module Cat No 1746 IA 16 IB 16 IC 16 IG 16 IH 16 IM 16 IN 16 ITB 16 ITV 16 IV 16 OA 16 OB 16 OB 16E OBP 16 OG 16 OV...

Page 36: ...1492 IFM40DS120A 4 16 Individually isolated with 240V AC LEDs and four terminals input 1492 IFM40DS240A 4 Fusible 40 Terminal IFMs Description Cat No I O Module Cat No 1746 IB 32 IV 32 OB 32 OB 32E OV 32 120V AC DC with extra terminals for outputs 1492 IFM40F F 2 H H H Extra terminals with 24V AC DC blown fuse indicators for outputs 1492 IFM40F F24 2 H H H Extra terminals with 120V AC DC blown fus...

Page 37: ...es 20 1746 IG16 OB16 OB16E OBP16 OG16 OV16 OVP16 1492 CABLE G 0 5 1 0 2 5 5 0 m Yes 20 1746 OA16 1492 CABLE H 0 5 1 0 2 5 5 0 m Yes 40 1746 IB32 IV32 OB32 OB32E OV32 1492 CABLE N 0 5 1 0 2 5 5 0 m Yes 20 1746 OW16 OX8 1492 CABLE S 0 5 1 0 2 5 5 0 m Yes 20 1746 OX8 Cables are available in standard lengths of 0 5 m 1 0 m 2 5 m and 5 0 m To order insert the code for the desired cable length into the ...

Page 38: ...own fuse indicators 1492 AIFMQS Q Pre Wired Cables for 1746 Analog I O Modules These pre wired cables have a pre wired RTB on one end to connect to the front of a Bulletin 1746 analog I O module and a connector on the other end to plug into a 20 or 40 terminal IFM To use this table you must first have selected an IFM from the preceding table Cable Cat No Standard Cable Lengths m Build to Order Ava...

Page 39: ...f communication services NetLinx architecture part of the Integrated Architecture seamlessly integrates all the components in an automation system from a few devices on one network to multiple devices on multiple networks including access to the Internet helping you to improve flexibility reduce installation costs and increase productivity The EtherNet IP network is an open industrial networking s...

Page 40: ...iagnostics for improved data collection and fault detection Less wiring and reduced startup time than traditional hard wired systems DeviceNet 1747 SDN DeviceNet Scanner Module 1761 NET DNI DeviceNet Interface Module Plant wide and cell level data sharing with program maintenance Data Highway Plus DH SLC 5 04 Processor DH 485 1747 KE DH 485 RS 232C Interface SLC 5 01 5 02 or 5 03 Processor with a ...

Page 41: ...X PWR CABLE EXTERNAL IP SLC 5 05 Controller Ethernet Hub Switch MicroLogix 1500 Controller 1761 NET ENI Module PC Ethernet Interface Card PC with RSLogix 500 and RSLinx Ethernet connectivity for SLC 500 is provided for the following SLC 5 05 processor 1761 NET ENI 1761 NET ENIW MicroLogix 1000 controllers may be used with the 1761 NET ENI or ENIW however some features are not supported Email ENI E...

Page 42: ...ps 10 100Base T Cat No 1761 NET ENI 1761 NET ENIW Description Ethernet Interface ENI Web Enabled Ethernet Interface ENIW 24V dc Current Draw Power Supply DC Voltage Range Isolation Voltage Inrush Current Max Communication Rate Ethernet Interface ControlNet Network The ControlNet network is an open high speed deterministic network used for transmitting time critical information It provides real tim...

Page 43: ...bility for an SLC 5 03 5 04 and 5 05 processor to send or receive unscheduled ControlNet messages With unscheduled messaging the SLC controller program can send peer to peer messages or be accessed and edited over the ControlNet network using RSLogix 500 software The 1747 KFC15 consumes 0 640 A at 5V dc The ControlNet Messaging Module features 4 digit 7 segment display for node address and module ...

Page 44: ...rm Discrete Analog 1746 1756 1771 1793 1794 1797 ControlNet Adapter Modules The 1747 ACN15 and ACNR15 modules enable up to three 1746 chassis of I O modules to produce consume scheduled I O on the ControlNet network Both modules are compatible with all 1746 discrete analog and specialty I O except those requiring G file configuration such as the 1747 SN and 1747 BSN modules The 1747 ACN15 and ACNR...

Page 45: ...ces from multiple vendors that meet DeviceNet standards are interchangeable Common network an open network provides common end user solutions and reduces the need to support a wide variety of device networks Lower maintenance costs replace devices without disrupting other devices Cost effective wiring one wire supplies communications and 24V dc power 1747 SDN Scanner 1770 KFD Module 1761 NET DNI M...

Page 46: ...ace allowing connection of DF1 compatible devices to a DeviceNet network where the DNI functions as a DeviceNet slave In addition the DNI enables the setup of a peer to peer communications network on DeviceNet with other devices using DNIs similar to a DH 485 or DH network This capability works between controllers between PCs and controllers and for program upload download I O and data messages ar...

Page 47: ... lengths communication rates and associated termination resistor sizes for the DH network DH Network Specifications Baud Rate Maximum Cable Distance Terminating Resistor Size 57 6 K baud 3048 m 10 000 ft 150 Ω 115 K baud 1542 m 5000 ft 150 Ω 230 4 K baud 762 m 2500 ft 82 Ω DH Network PC with 1784 PKTX or PKTXD PLC 5 Controller PLC 5 Controller with 1785 KA5 SLC 5 04 1747 NET AIC Module 1747 AIC Mo...

Page 48: ...ccess control and the ability to add or remove nodes without disrupting the network DH 485 supports slave devices and features multiple master capability PC with USB Port PC 1747 UIC Module 1747 AIC Module PanelView Terminal SLC 5 02 Controller SLC 5 03 Controller or higher 1747 AIC Module 1747 NET AIC Module 24V dc User Power The SLC 500 family includes the following DH 485 devices 1747 KE DH 485...

Page 49: ...requirements for the 1747 KE when estimating the total requirements for your system If the 1747 AIC Link Coupler is connected to the 1747 KE module with a 1747 C13 cable the power for the link coupler comes from either an SLC 500 processor or an external power supply Therefore current requirements remain as listed Cat No 1747 KE Backplane Current mA at 5V 150 mA Backplane Current mA at 24V 40 mA R...

Page 50: ...erial Bus to DH 485 Interface Converter This device allows a computer with a USB port to interface to DH 485 ports on an SLC 500 MicroLogix or other Rockwell Automation controllers and on PanelView terminals The 1747 UIC features a USB connector as well as both an RS 232 and an RS 485 port Use the RS 232 port to connect to SLC 5 03 5 04 5 05 Channel 0 MicroLogix CompactLogix FlexLogix ControlLogix...

Page 51: ...hassis reduces installation start up and maintenance costs by placing the I O closer to the sensors and actuators SLC 5 03 5 04 and 5 05 processors support pass thru which lets you configure RIO devices remotely from an Ethernet DH or DH 485 DF1 network as well as block transfer instructions for faster reading and writing of I O data SLC 5 03 Controller SLC 5 04 Controller SLC 5 02 Controller Pane...

Page 52: ... change applications in PanelView terminals and Power monitors via remote I O passthru Remote I O Scanner Module The 1747 SN module provides high speed remote communication between an SLC processor and Allen Bradley operator interface and control devices The scanner provides connectivity of your SLC 5 02 or higher processor to devices such as InView Message displays Power Monitor 3000 PanelView 17...

Page 53: ...f a fault in the primary system The 1747 BSN features backup of one Remote I O or DH network per complementary BSN module pair backup of one RS 232 DH 485 communications per complentary BSN module pair allowing HMIs on channel 0 to automatically transfer to the primary processor transfer of up to 2 K words of retentive data per BSN repair of primary system fault during secondary backup system oper...

Page 54: ...supports and the chassis size of the DCM The SLC 500 module controllers support multiple DCMs Note An important distinction between a DCM module and the 1747 ASB module is that a DCM is placed in the chassis with the processor and it does not scan any I O in the chassis as an ASB module does Remote I O Device Specifications Remote I O Device Catalog Numbers and Specifications Cat No Description Ba...

Page 55: ...es In point to point mode the SLC 500 controller uses DF1 full duplex protocol DF1 half duplex master polls and transmits messages between the master and each remote node In master mode the SLC 500 controller uses DF1 half duplex polled protocol DF1 half duplex slave uses the controller as a slave station in a master slave serial network In slave mode the SLC 500 controller uses DF1 half duplex pr...

Page 56: ...rt splitter has fully isolated communication ports Therefore no external isolation is required The Prog HMI port connects to a programming station or HMI device PanelView Standard PanelView Plus VersaView CE for respond only operations The serial configuration for the Network and Programmer HMI ports on the 1747 DPS1 port splitter must be set to DF1 full duplex 8 bits no parity 1 stop bit 19 2 K b...

Page 57: ...05 Channel 0 or other controller with RS 232 DF1 Full Duplex Port Ethernet IP Network Operator Interface RS 232 DF1 Port Splitter 1761 NET AIC Module DeviceNet Network PC Programming Terminal 24V dc 100 mA Class 2 Power Supply www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 58: ...o the Isolated Link Coupler 1747 AIC 1747 C13 Specialty Module to Isolated Link Coupler Cable Use a 1747 C13 cable to connect a BASIC or KE module to an Isolated Link Coupler 1747 AIC Also connects 1747 UIC RS 485 port to AIC or SLC RJ45 port Cable Connectivity Summary For Connectivity Between These Devices Preferred Cable Catalog Number These Cables May Be Used 1746 A4 A7 A10 or A13 Chassis 1746 ...

Page 59: ...provides 8 K 16 K or 32 K of memory A built in RS 232 channel gives you the flexibility to connect to external intelligent devices without the need for additional modules Modular I O systems can be configured with a maximum of 3 chassis 30 total slots and from 4 I O points to a maximum of 4096 I O points SLC 5 04 The standard DH 485 port has been replaced with a DH port providing high speed SLC 5 ...

Page 60: ...al Scan Time 8 ms K 4 8 ms K 1 ms K 0 9 ms K Program Scan Hold up Time After Loss of Power 20 ms 3 s dependent on power supply loading Bit Execution XIC 4 μs 2 4 μs 0 44 μs 0 37 μs Clock Calendar Accuracy N A 54 seconds month 25 C 77 F 81 seconds month 60 C 140 F The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and communication servicing Actual scan times...

Page 61: ...N LOG SIN TAN XPY RMP Logical perform logical operations on bits AND OR XOR NOT Conversion perform conversion between integer and BCD values and radian and degree values TOD FRD DCD DEG RAD ENC Move move and modify bits MOV MVM RPC File perform operations of file data COP FLL BSL BSR FFL FFU LFL LFU FBC DDT Sequencer monitor consistent and repeatable operations SQO SQC SQL Program Control change t...

Page 62: ...evice The 1747 PSD simplifies PLC program development backup and upgrade shipping issues for SLC 5 03 and higher processors as well as MicroLogix controllers The PSD allows you to upload and download to your industrial programming station using RSLogix 500 software back up PLC programs without using a computer or programming software make multiple copies of an installed program Before downloading ...

Page 63: ...de Kit Labels includes 10 labels 1747 RL401 SLC 5 04 Upgrade Kit Labels includes 10 labels 1747 RL501 SLC 5 05 Upgrade Kit Labels includes 10 labels 1747 BA Lithium Battery Assembly Backup power for RAM is provided by a replaceable lithium battery The lithium battery provides backup for approximately five years for the 1747 L511 and two years for the 1747 L514 It provides backup for approximately ...

Page 64: ... interconnect cables not included If an interconnect cable is required select a chassis interconnect cable from the following table Chassis and Cable Descriptions Cat No Description 1746 A4 4 Slot Chassis 1746 A7 7 Slot Chassis 1746 A10 10 Slot Chassis 1746 A13 13 Slot Chassis 1746 C7 Chassis Interconnect Cable ribbon cable used when linking modular style chassis up to 152 4 mm 6 in apart in an en...

Page 65: ...ssis Installation Instructions publication number 1746 IN016 for more information 4 Slot Modular Chassis 261 10 28 235 9 25 215 8 46 145 5 71 171 6 73 140 5 51 158 6 22 140 5 51 171 6 73 70 2 76 14 0 55 11 Dia 0 433 5 5 Dia 0 217 1 0 0 04 45 Dia 1 77 5 5 Dia 0 217 Left Side View Front View millimeters inches 1 Dimensions for 1746 P1 Power Supply 2 Dimensions for 1746 P2 P3 P5 P6 and P7 Power Suppl...

Page 66: ...0 Slot Modular Chassis 481 18 94 455 17 91 435 17 13 171 6 73 140 5 51 145 5 71 140 5 51 140 5 51 140 5 51 158 6 22 1 0 0 04 55 2 17 5 5 Dia 0 217 11 Dia 0 433 14 0 55 5 5 Dia 0 217 1 Dimensions for 1746 P1 Power Supply 2 Dimensions for 1746 P2 P3 P5 P6 and P7 Power Supplies 3 Dimensions for 1746 P4 Power Supply Front View Left Side View millimeters inches 1 2 3 www aotewell com www fa market com ...

Page 67: ... 433 5 5 Dia 0 217 5 5 Dia 0 217 14 0 55 1 2 3 145 5 71 171 6 73 140 5 51 1 0 0 04 Left Side View Front View millimeters inches 1 Dimensions for 1746 P1 Power Supply 2 Dimensions for 1746 P2 P3 P5 P6 and P7 Power Supplies 3 Dimensions for 1746 P4 Power Supply www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 68: ... determine which power supply is appropriate for your system You need one worksheet for each chassis TIP Consider future system expansion when choosing power supplies The SLC system features three AC power supplies and four DC power supplies The power supply mounts on the left side of the chassis with two screws For AC power supplies 120 240 volt selection is made by placing the jumper to match th...

Page 69: ... A 24V dc 20 A 1746 P7 10 30V dc isolated 12V dc input 2 A 24V dc input 3 6 A 12V dc input 0 46 A 24V dc input 0 87 A 20 A Total of all output power 5V backplane 24V backplane and 24V user source must not exceed 70 W General 1746 Px Power Supply Specifications Specification Description Operating Temperature 0 60 C 32 140 F Current capacity derated by 5 above 55 C for P1 P2 P3 P5 P6 and P7 no derat...

Page 70: ...nternal current capacity for 1746 P1 is 2 A at 5V dc and 0 46 A at 24V dc Slot Numbers Description Cat No Backplane Current at 24V dc 0 Processor Unit 1747 L514 0 105 A 1 Output Module 1747 OW16 0 180 A 2 Combination Module 1746 IO12 0 070 A 3 4 5 6 Analog Output Modules 1746 NO4I 0 780 A 4 x 0 195 Peripheral Device Isolated Link Coupler 1747 AIC 0 085 A Peripheral Device USB to DH 485 Interface 1...

Page 71: ...o step 4 Current Multiply By Watts Current Multiply by Watts Total Current at 5V dc 0 905 A 5V 4 525 W Total Current at 5V dc 0 830 A 5V 4 15 W Total Current at 24V dc 0 190 A 24V 4 56 W Total Current at 24V dc 1 220 A 24V 29 28 W User Current at 24V dc 0 500 A 24V 12 00 W User Current at 24V dc 0 500 A 24V 12 00 W Add the Watts values to determine Total Power cannot exceed 70 W 21 085 W Add the W...

Page 72: ...o Backplane Current mA at 5V Backplane Current mA at 24V Watts per Point Thermal Dissipation Min Thermal Dissipation Max 1746 IA4 35 mA 0 mA 0 270 W 0 175 W 1 30 W 1746 IA8 50 mA 0 mA 0 270 W 0 250 W 2 40 W 1746 IA16 85 mA 0 mA 0 270 W 0 425 W 4 80 W 1746 IB8 50 mA 0 mA 0 200 W 0 250 W 1 90 W 1746 IB16 50 mA 0 mA 0 200 W 0 425 W 3 60 W 1746 IB32 106 mA 0 mA 0 200 W 0 530 W 6 90 W 1746 IC16 50 mA 0...

Page 73: ... 0 338 W 1 40 W 7 60 W 1746 OV32 190 mA 0 mA 0 078 W 2 26 W 4 80 W 1746 OVP16 250 mA 0 mA 0 310 W 1 25 W 6 21 W 1746 OW4 45 mA 45 mA 0 133 W 1 31 W 1 90 W 1746 OW8 85 mA 90 mA 0 138 W 2 59 W 3 70 W 1746 OW16 170 mA 180 mA 0 033 W 5 17 W 5 70 W 1746 OX8 85 mA 90 mA 0 825 W 2 59 W 8 60 W Power supply loading for series D and later modules Digital Combination Modules Cat No Backplane Current mA at 5V...

Page 74: ...n Min Thermal Dissipation Max 1746 NO4I 55 mA 195 mA N A 4 96 W 5 00 W 1746 NO4V 55 mA 145 mA N A 3 78 W 3 80 W 1746 NO8I 120 mA 250 mA N A 2 44 W 6 6 W 1746 NO8V 120 mA 160 mA N A 1 98 W 4 44 W With jumper set to RACK otherwise 0 000 Analog Combination Modules Cat No Backplane Current mA at 5V Backplane Current mA at 24V Watts per Point Thermal Dissipation Min Thermal Dissipation Max 1746 FIO4I 5...

Page 75: ... Dissipation Min Thermal Dissipation Max 1747 ACN15 900 mA 0 mA N A 4 50 W 4 50 W 1747 ACNR15 900 mA 0 mA N A 4 50 W 4 50 W 1747 ASB 375 mA 0 mA N A 1 875 W 1 875 W 1747 BSN 800 mA 0 mA N A 4 00 W 4 00 W 1747 DCM 360 mA 0 mA N A 1 80 W 1 80 W 1747 KE 150 mA 40 mA N A 3 75 W 3 80 W 1747 KFC15 640 mA 0 mA N A 3 20 W 3 20 W 1747 SCNR 900 mA 0 mA N A 4 50 W 4 50 W 1747 SDN 500 mA mA N A 2 50 W 2 50 W ...

Page 76: ...0 25 Power Supply Loading Watts 30 35 5 10 15 20 25 1746 P4 Power Supply Change in Power Dissipation due to Output Loading 0 10 20 30 40 50 Power Supply Loading Watts 60 70 80 0 5 10 15 20 25 Power Supply Dissipation Watts 1746 P5 Power Supply Change in Power Dissipation due to Output Loading 0 2 4 6 8 10 12 14 16 18 20 Power Supply Dissipation Watts 0 5 10 15 20 25 Power Supply Dissipation Watts ...

Page 77: ...5 17 3 1746 OV8 0 675 7 1746 OW16 5 17 User Power User Power 2 4 User Power Peripheral Device 1747 DTAM 2 5 Peripheral Device Peripheral Device 4 Add the heat dissipation values together for your power supply loading 8 925 4 Add the heat dissipation values together for your power supply loading 13 59 4 Add the heat dissipation values together for your power supply loading 5 Use the power supply lo...

Page 78: ... editing lets you quickly move or copy instructions from rung to rung within a project rungs from one subroutine or project to another or data table elements from one data file to another Context menus for common software tools are quickly accessible by clicking the right mouse button on addresses symbols instructions rungs or other application objects This convenience provides you with all the ne...

Page 79: ...pulate the data in your favorite spreadsheet program When finished simply import the CSV file into RSLogix 500 Diagnostics and Troubleshooting Tools Quickly locate the specific area in the application that is causing a problem with Advanced Diagnostics Diagnose the interaction of output instructions within a section of your program by viewing them at the same time Simultaneously examine the status...

Page 80: ...Data Monitor Report Intellisense style Address Wizard Recipe Monitor Reprot User Workspace Smart I O Configuration Report Instruction Pallette Margins Header Footer Portal Dot Commands Custom Title Page Intelligent Goto Automation Project Backup Span Volume Author Microsoft VBA Scripts Secondary Save Path Execute Microsoft VBA Scripts Network Configuration RSNetWorx Cnet Dnet ENet included Keyboar...

Page 81: ...res 1784 CP13 1784 PCMK requires 1784 PCM4 requires 1784 PCM6 1784 U2DHP 10 100Base T Ethernet Warranty Rockwell Software provides a full one year limited warranty for RSLogix 500 programming software products Support Continuation Agreements You can purchase additional one year terms of support Orders for support continuation agreements must be accompanied by your name address software serial numb...

Page 82: ...ese operating systems Microsoft Windows Vista Microsoft Windows XP Microsoft Windows 2000 In most cases RSLinx Lite software comes bundled with controller programming software packages You can also download RSLinx Lite for free from the Software Updates link on the Get Support Now website at http support rockwellautomation com Cat No RSLinx Products Available only bundled with other products such ...

Page 83: ...e software automatically calculates network bandwidth for the entire network as well as the bandwidth used by each network component You must have RSNetWorx software to configure and schedule ControlNet networks DeviceNet software to configure DeviceNet I O devices and create a scan list The DeviceNet scanner stores the configuration information and scan list EtherNet IP software to configure Ethe...

Page 84: ...e with MD RSNetWorx software can be used with these operating systems Microsoft Windows Vista Microsoft Windows XP Microsoft Windows 2000 In some cases RSNetWorx software comes bundled with controller programming software packages Test and debug all of your ladder logic programs prior to commissioning and startup RSLogix Emulate 500 software is a Microsoft Windows software package that emulates on...

Page 85: ... 120V ac Digital Outputs 25 1746 OA8 8 4 24V dc Digital Inputs 43 1746 IB16 16 3 24V dc Digital Outputs 17 1746 OB16 16 2 Isolated Relay Outputs 11 1746 OX8 8 2 4 20 mA Analog Inputs 7 1746 NI8 8 1 Remote I O Scanner N A 1747 SN N A 1 Power Supply N A 1746 Px N A 3 SLC 500 Processor N A 1746 L5xx N A 1 Card Slot Fillers N A 1746 N2 N A 3 SLC 500 Chassis N A 1746 A7 N A 1 1746 A10 2 PanelView Termi...

Page 86: ...cessor memory I O speed and programming requirements memory modules adapter sockets 4 Select an SLC 500 Chassis chassis with slots for required modules and for additional modules to support future growth card slot fillers 1746 N2 for open slots interconnect cables 5 Select an SLC 500 Power Supply power supply loading of the entire system additional capacity for system expansion 6 Select Programmin...

Page 87: ...dc 5V Total Current at 24V dc 24V Total Current at 24V dc 24V User Current at 24V dc 24V User Current at 24V dc 24V Add the Watts values to determine Total Power cannot exceed 70 W Add the Watts values to determine Total Power cannot exceed 70 W 4 Choose the power supply from the list of catalog numbers below Compare the Total Current required for the chassis with the Internal Current capacity of ...

Page 88: ...ral Dev 4 Add the heat dissipation values together for your power supply loading 4 Add the heat dissipation values together for your power supply loading 4 Add the heat dissipation values together for your power supply loading 5 Use the power supply loading step 4 for each chassis and the graphs on page 76 to determine power supply dissipation 5 Use the power supply loading step 4 for each chassis...

Page 89: ...89 Publication 1747 SG001D EN P January 2009 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 90: ...90 Publication 1747 SG001D EN P January 2009 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 91: ...91 Publication 1747 SG001D EN P January 2009 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...

Page 92: ...opyright 2009 Rockwell Automation Inc All Rights Reserved Printed in USA Supersedes Publication 1747 SG001C EN P September 2007 www aotewell com www fa market com info aotewell com AoteWell International inc sales aotewell com Tel 852 6563 2160 ...