2-184 Parameter
Descriptions
7000-TD002A-EN-P – September 2007
Drive4 Status [Drive4 Status]
Linear Number:
728
Access Level:
Advanced
Read/Write:
Read
Only
These eight variables display the status of all the drives in a parallel drive system. They are valid in the
master drive only, and will have a value of zero in all slave drives. The definition is the same as
PD Status
.
Bit
Enum Text
Description
0
Ready
Drive is ready
1
Running
Drive is running
2
Faulted
Drive has a fault condition
3
Class1 Fault
Drive has a class 1 fault
4
Class2 Fault
Drive has a class 2 fault
5
Hub Comm OK
Communications between the drive and the hub PLC is functional
6
Input Clsed
Drive input contactor is closed
7
Output Clsed
Drive output contactor is closed
8 Unused
9 Unused
10 Unused
11 Unused
12 Unused
13 Unused
14 Unused
15
Status Valid
Status word is valid
Drive5 Status [Drive5 Status]
Linear Number:
729
Access Level:
Advanced
Read/Write:
Read
Only
These eight variables display the status of all the drives in a parallel drive system. They are valid in the
master drive only, and will have a value of zero in all slave drives. The definition is the same as
PD Status
.
Bit
Enum Text
Description
0
Ready
Drive is ready
1
Running
Drive is running
2
Faulted
Drive has a fault condition
3
Class1 Fault
Drive has a class 1 fault
4
Class2 Fault
Drive has a class 2 fault
5
Hub Comm OK
Communications between the drive and the hub PLC is functional
6
Input Clsed
Drive input contactor is closed
7
Output Clsed
Drive output contactor is closed
8 Unused
9 Unused
10 Unused
11 Unused
12 Unused
13 Unused
14 Unused
15
Status Valid
Status word is valid
Summary of Contents for PowerFlex 7000
Page 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Page 2: ......
Page 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Page 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Page 244: ......
Page 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Page 349: ......