2-12 Parameter
Descriptions
7000-TD002A-EN-P – September 2007
Drive Not Ready Status Word 2 [Drive Not Ready2]
Linear Number:
699
Access Level:
Monitor
Read/Write:
Read
Only
This parameter specifies the status of several different conditions that can cause a Drive Not Ready
indication. ‘1’ in the corresponding bit location indicates that condition exists, and ‘0’ indicates that the
condition does not exist. The following is description of the individual bits:
Bit
Enum Text
Description
0
SCR Gate Pwr
The self powered gate drive boards for SCR drives are not charged
1
InpCtctrOpen
The Drive Input Contactor is Open when it should not be
2 Unused
3 Unused
4 Unused
5 Unused
6 Unused
7 Unused
8 Unused
9 Unused
10 Unused
11 Unused
12 Unused
13 Unused
14 Unused
15 Unused
Drive Status Flags 1 [DrvStatus Flag1]
Linear Number:
569
Access Level:
Service
Read/Write:
Read
Only
This parameter specifies the drive status flags. Each bit has 2 states, and that allows the parameter to
represent 16 conditions. They are as shown below:
Bit
0 – Enum Text
1 – Enum Text
0 Not
Ready
Ready
1 Not
Running
Running
2
Forward Rotation
Reverse Rotation
3 No
Faults
Faulted
4 No
Warnings
Warnings
5
Fans Off
Fans On
6
Input Open
Input Closed
7
Output Open
Output Closed
Summary of Contents for PowerFlex 7000
Page 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Page 2: ......
Page 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Page 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Page 244: ......
Page 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Page 349: ......