Parameter Descriptions
2-17
7000-TD002A-EN-P – September 2007
Inverter Control Flags 3 [InvControl Flag3]
Linear Number:
446
Access Level:
Service
Read/Write:
Read
Only
This word indicates various status bits within the inverter control. The word can be used in trending to
assist in determining what the rectifier control is doing in a normal or abnormal situation. A 1 in a location
indicates that condition is active, and a 0 indicates the condition is inactive.
Bit
Enum Text
Description
0
PF Achieved
Desired power factor compensation has been achieved
1
RestartExprd
AutoRestart Delay timer has expired
2
PFC Leading
Leading Power factor compensation has been enabled
3
Out Dschrgd
Motor filter capacitors have been discharged to 5% of rated
4
UWV Seq
UWV Sequence enabled
5
IsoTx Fan1
Isolation Transformer 1 Fan is ON
6
IsoTx Fan2
Isolation Transformer 2 Fan is ON
7
ESP Drive
ESP Drive selected
8
Restart Mode
Auto Restart mode enabled
9
Cool Fans On
Drive Cooling Fans ON
10
PFC Optimal
Optimal Power factor compensation has been enabled
11
PFC Mod Ctrl
Power factor compensation using modulation index control
12
Flying Strt1
Flying Start State 1
13
Flying Strt2
Flyig Start State 2
14
Flying Start
Flying Start mode is active
15
PFC FlxRange
Flux limit has been reached while compensating for line power factor
Inverter Analog Self Test Code 1 [InvAnlg SelfTst1]
Linear Number:
96
Access Level:
Service
Read/Write:
Read
Only
This parameter specifies the power-up diagnostic results on the Analog Control Board. It refers to the
signals used by the inverter (Slave) processor. If the software detects a problem with the analog signals
into the board, or the board itself, an
InvAnlg SelfTest
fault will appear. This parameter will help indicate
which signals are causing the problem. The action should be to investigate all the connections and
feedback paths related to that signal before changing the ACB or the DPM. This is a self-test fault that
will only occur at initial power-up.
Bit
Enum Text
Description
0
HECSU Offset
Phase U Motor Current Offset High
1
HECSW Offset
Phase V Motor Current Offset High
2
UV Offset
Phase UV Motor Voltage Offset High
3
VW Offset
Phase VW Motor Voltage Offset High
4
VSAB Offset
Bypass UV Voltage Offset High
5
VSBC Offset
Bypass VW Voltage Offset High
6
2UV Offset
Master Bridge Phase UV Voltage Offset High (for Synch. Transfer)
7
2VW Offset
Master Bridge Phase VW Voltage Offset High (for Synch. Transfer)
8
VMDC1 Offset
Motor Side DC Link Voltage Offset High
9
VMDC2 Offset
Motor Side DC Link Voltage Offset High
10
UV_2 Offset
Phase UV Motor Voltage Offset High (used for low motor voltage)
11
VW_2 Offset
Phase VW Motor Voltage Offset High (used for low motor voltage)
12
MFCN Offset
Motor Filter Capacitor Neutral Voltage Offset High
13
VZS Offset
Motor Zero Sequence Voltage Offset High
14
UV_NF Offset
Unfiltered Phase UV Motor Voltage Offset High
15
VW_NF Offset
Unfiltered Phase VW Motor Voltage Offset High
Contact factory for availability
Summary of Contents for PowerFlex 7000
Page 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Page 2: ......
Page 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Page 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Page 244: ......
Page 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Page 349: ......