Parameter Descriptions
2-15
7000-TD002A-EN-P – September 2007
Rectifier Control Flags 2 [RecControl Flag2]
Linear Number:
160
Access Level:
Service
Read/Write:
Read
Only
This word indicates various status bits within the rectifier control. The word can be used in trending to
assist in determining what the rectifier control is doing in a normal or abnormal situation. A 1 in a location
indicates that condition is active, and a 0 indicates the condition is inactive.
Bit
Enum Text
Description
0
RecClass1Flt
A Rectifier Class 1 fault exists
1
RecClass2Flt
A Rectifier Class 2 fault exists
2
Rec Warning
A Rectifier Warning exists
3
PhsngChkDone The drive has completed the input phasing checks
4
No PLL Error
There is no problems with the PLL Lock
5
Offline Diag
The rectifier has completed the offline device diagnostics
6
FreeWhl Rec
The rectifier is in Free-Wheel mode (caused by Bus Transients)
7
FreeWhl Inv
The inverter is in Free-Wheel mode (caused by Bus Transients)
8
Device Short
The Rectifier has detected a shorted device
9
BusTransient
There is a transient detected on the input of the drive
10
FreeWhlReset
Handshake for Freewheel Mode
11
RecSGCT Pwr
Rectifier SGCTs have Power
12
RtdLimit Req
Drive is requested to go into Retard Limit
13
InvAdvLmtReq
Inverter is requested to go into Advance Limit
14
Drv OL Pend
Drive Overload is Timing
15
Rec Crit Flt
Rectifier has detected a Critical Fault
Rectifier Control Flags 3 [RecControl Flag3]
Linear Number:
368
Access Level:
Service
Read/Write:
Read
Only
This word indicates various status bits within the rectifier control. The word can be used in trending to
assist in determining what the rectifier control is doing in a normal or abnormal situation. A 1 in a location
indicates that condition is active, and a 0 indicates the condition is inactive.
Bit
Enum Text
Description
0
No Flt Delay
Internal fault timers disabled
1
Act Dschrge
Active discharge
2
Lnk Dschrge
DC Link Voltage Discharge
3
Lnk PDschrge
DC Link Voltage Pre Discharge
4
Gate Enbl Rq
Gate enable request
5
SCR Gate Pwr
SCR Gate Power
6
Inp Open Req
Input Open Request
7
Gnd OC Disbl
Ground OC disabled
8
BusTran Enbl
Bus Transient enabled
9
DvcLineShort
Device Line to Line short
10
DvcCMVE Shrt
Device CMVE SC
11
InpLockOut
Due to Line Over Current condition, the input contactor is being
prevented from closing (18P only)
12
InpLock5min
Due to Line Over Current condition, the input contactor is being
prevented from closing for 5 minutes(18P only)
13
InpLockIndef
Due to Line Over Current condition, the input contactor is being
prevented from closing indefinitely (18P only).
14
Inp Dschargd
Line filter capacitors have been discharged
15 RecFlg3Bit15
Unused
bit
Summary of Contents for PowerFlex 7000
Page 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Page 2: ......
Page 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Page 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Page 244: ......
Page 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Page 349: ......