Parameters Listed by Group
2-211
7000-TD002A-EN-P – September 2007
Drive Protection Parameters
Name
Min.
Max.
Default
Units
Read-
Only
Access
169 DCLnk OvrCur Trp
0.00
4.00
1.75
pu
N
Advanced
170 DCLnk OvrCur Dly
0
100
10
msec
N
Advanced
161 Line OvrCur Trp
0.00
4.00
1.75
pu
N
Advanced
162 Line OvrCur Dly
0
100
10
msec
N
Advanced
165 Line OvrVolt Trp
0.00
2.00
1.20
pu
N
Advanced
166 Line OvrVolt Dly
0
1000
10
msec
N
Advanced
173 Rec OvrVolt Trp
0.00
2.00
1.50
pu
N
Advanced
174 Rec OvrVolt Dly
0
100
10
msec
N
Advanced
193 Inv OvrVolt Trp
0.00
2.00
1.50
pu
N
Advanced
194 Inv OvrVolt Dly
0
100
10
msec
N
Advanced
271 LineVoltUnbalTrp
0.00
1.00
0.05
pu
N
Advanced
272 LineVoltUnbalDly
0.0
10.0
1.0
sec
N
Advanced
108 Line CurUnbalTrp
0.00
1.00
0.05
pu
N
Advanced
109 Line CurUnbalDly
0.0
10.0
1.0
sec
N
Advanced
167 Line UndVolt Lvl
0.40
1.50
0.85
pu
N
Advanced
168 Line UndVolt Dly
0
100
17
msec
N
Advanced
270 Drv OvrLoad Wrn
0.00
1.00
0.50
N
Advanced
772 Drv Thermal Cyc
0.0
6000.0
600.0
sec
N
Advanced
163 Drv OvrLoad Trp
0.00
4.00
1.15
pu
N
Advanced
164 Drv OvrLoad Dly
0.0
600.0
60.0
sec
N
Advanced
269 Drv OvrLoad Min
0.00
4.00
1.05
pu
N
Advanced
587
LineNeutVoltTrp 0.00 1.50 0.40
pu
N
Advanced
588 LineNeutVoltDly
0.0
10.0
1.0
sec
N
Advanced
171 Gnd OvrCur Trp
0.05
10.00
0.50
A
N
Advanced
172 Gnd OvrCur Dly
0.0
10.0
0.1
sec
N
Advanced
675 Harmonic VoltTrp
0.00
10.00
0.30
pu
N
Advanced
676 Harmonic VoltDly
0.0
10.0
1.0
sec
N
Advanced
774 RNeut
OvrLoadTrp
0.00
655.35 5.00
N
Service
775 RNeut OvrLoadDly
0.00
655.35
2.50
sec
N
Service
776 RNeut
OvrCurTrp
0.00
655.35 10.00
N
Service
777 RNeut OvrCurDly
0.000
65.535
0.010
sec
N
Service
673 BusTransTrpFac
0.00
100.00
2.50
pu
N
Service
674 BusTransient Dly
0
100
2
N
Service
677 BusTrans MinTrp
0.00
10.00
0.30
pu
N
Service
678 BusTrans IdcFac
0.00
10.00
0.50
pu
N
Service
679 Min Freewhl Time
0.000
1.000
0.016
sec
N
Service
698 Line Loss Trip
0.0
40.0
8.0
Hz
N
Service
266 Rec Dvc Diag Dly
0
6
2
N
Service
268 Inv Dvc Diag Dly
0
6
2
N
Service
112 RecHSink
TempWrn 0
100
53
C
N
Service
111 RecHSink TempTrp
0
100
55
C
N
Service
316 InvHSink
TempWrn
0
100
61
C
N
Service
315 InvHSink TempTrp
0
100
64
C
N
Service
656 IsoTx
AirFlowNom
0.0
10.0
3.6
V
N
Service
655 IsoTx AirFlowWrn
0.0
10.0
3.0
V
N
Service
654 IsoTx
AirFlowTrp
0.0
10.0
2.5
V
N
Service
317 Conv AirFlow Nom
0.0
10.0
3.6
V
N
Service
320 Conv AirFlow Wrn
0.0
10.0
3.0
V
N
Service
319 Conv AirFlow Trp
0.0
10.0
2.5
V
N
Service
Summary of Contents for PowerFlex 7000
Page 1: ...PowerFlex 7000 Medium Voltage AC Drive TECHNICAL DATA Firmware Version 7 xxx ...
Page 2: ......
Page 4: ...ii Table of Contents 7000 TD002A EN P September 2007 ...
Page 44: ...1 40 Functional Description 7000 TD002A EN P September 2007 ...
Page 244: ......
Page 346: ...3 58 Troubleshooting 7000 TD002A EN P September 2007 ...
Page 349: ......