![Rockwell Automation CNMD180W0ENNNC1 User Manual Download Page 75](http://html.mh-extra.com/html/rockwell-automation/cnmd180w0ennnc1/cnmd180w0ennnc1_user-manual_1475500075.webp)
Parameter Descriptions
3-49
Defines the amount of time at or above Wake Level before a start command is issued.
Defines the analog input level that will stop the drive.
Defines the amount of time at or below Sleep Level before a stop command is issued.
Sets the reaction to a loss of input power. Power loss is recognized when:
DC bus voltage is
≤
73% of DC Bus Memory and Power Loss Mode is set to Coast. DC
bus voltage is
≤
82% of DC Bus Memory and Power Loss Mode is set to Decel.
181
Wake Time
Range:
0.0 to 1000.0 Secs [0.1 sec]
Default:
0.0 sec
Access:
1
Path:
Dynamic Control>Restart Modes
See also:
180
182
Sleep Level
Range:
4.000 mA, 0.000 V / Wake Level [0.001 mA, 0.001 V]
Default:
5.000 mA, 5.000 V
Access:
1
Path:
Dynamic Control>Restart Modes
See also:
183
183
Sleep Time
Range:
0.0 to 1000.0 secs [0.1 sec]
Default:
0.0 sec
Access:
1
Path:
Dynamic Control>Restart Modes
See also:
182
184
Power Loss Mode
Range:
0 = Coast
1 = Decel
2 = Continue
3 = Coast input
4 = Decel input
Default:
0 = Coast
Access:
1
Path:
Dynamic Control>Power Loss
See also:
13, 184