Parameter Descriptions
3-11
Enables/disables the compensation correction options.
Reflect Wave =
Enables/disables reflected wave correction software, which reduces
overvoltage transients from the drive to the motor. For lead lengths beyond 300 feet,
enable this feature
.
Figure 3.1 – Speed Limits
Frequency
Overspeed
Limit
(83)
Frequency Trim
due to Speed
Control Mode
Max Volts
(54)
Motor Volts
(41)
Run
Boost
(70)
Break Volts
(71)
Start Boost
(69)
Allowable Output Frequency Range - Normal Operation
Allowable Speed Reference Range
Allowable Output Frequency Range -
Bus Regulation or Current Limit
Maximum
Freq
(55)
Motor NP Hz
(43)
0
Break
Frequency
(72)
Max
Speed
(82)
Min
Speed
(81)
Output
Freq Limit
V
o
l
t
a
g
e
56
Compensation
Range:
See figure 3.2
Default:
See figure 3.2
Access:
2
Path:
Motor Control>Torq Attributes
See also:
Figure 3.2 – Compensation (56)
1
0
1
1
1
0
x
0
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
=Enabled
0
=Disabled
x =Reserved
Bit #
Factory Default Bit Values
(1)
For current limit (except FVC Vector mode).
Reflect W
av
e
Enab
le Jerk
(1)
Ixo A
utoCalc
Xsistor Dia
g
Rs Adapt
Mtr Lead Re
v
PWM FreqLoc
k
TPEncdless
0