4-6
DBT Reach Drive User Manual
TB Man
Ref Cflct
30
➁
Occurs when:
•
“Auto/Manual” is selected (default) for Digital ln3 Sel (363) and
•
TB Man Ref Sel (96) has been reprogrammed.
No other use for the selected analog input may be programmed.
Example: If TB Man Ref Sel is reprogrammed to “Analog ln 2,” all of
the factory default uses for “Analog ln 2” must be reprogrammed.
To correct:
•
Verify/reprogram the parameters that reference an analog input or
•
Reprogram Digital ln3 to another function or “Unused.”
TorqProve
Cflct
49
➁
When TorqProve Cnfg is enabled, Motor CntlSel, Feedback Select,
and Motor Fdbk Type must be properly set.
Under-
Voltage
2
➀
The bus voltage has dropped below a predetermined value.
VHz Neg
Slope
24
➁
Custom V/Hz mode has been selected in Torq Perf Mode (53) and
the V/Hz slope is negative.
Waking
11
➀
The Wake timer is counting toward a value that will start the drive.
Table 4.3 – Alarm Names Cross-Referenced by Alarm Numbers
No.
1
1.Alarm numbers not listed are reserved for future use.
Alarm
No.
1
Alarm
No.
1
Alarm
1
Precharge Active
13
ln Phase Loss
25
IR Volts Range
2
UnderVoltage
14
Load Loss
26
FluxAmps Ref Rang
3
Power Loss
15
Ground Warn
27
Speed Ref Cflct
4
Start At PowerUp
17
Dig ln ConflictA
28
Ixo Vlt Rang
5
Analog In Loss
18
Dig ln ConflictB
29
Sleep Config
6
IntDBRes OvrHeat
19
Dig ln ConflictC
30
TB Man Ref Cflct
8
Drive OL Level 1
20
Bipolar Conflict
31
PTC Conflict
9
Drive OL Level 2
21
Motor Type Conflict
32
Brake Slipped
10
Decel Inhibit
22
NP Hz Conflict
34
Home Not Set
11
Waking
23
MaxFreq Conflict
49
Torq Prove Cflct
12
Motor Thermistor
24
VHz Neg Slope
50
Prof Step Cflct
Table 4.2 – Alarm Descriptions (Continued)
Alarm
No
.
Ty
p
e
Description