![Rockwell Automation CNMD180W0ENNNC1 User Manual Download Page 51](http://html.mh-extra.com/html/rockwell-automation/cnmd180w0ennnc1/cnmd180w0ennnc1_user-manual_1475500051.webp)
Parameter Descriptions
3-25
Scales the lower value of the TB Man Ref Sel selection when the source is an analog
input.
Displays the pulse input value as seen at terminals 5 and 6 of the Encoder Terminal
Block if Encoder Z Chan (423) is set to “Pulse Input.”
Sets the output frequency/speed when a jog command is issued. Units are selected
by Speed Units (79).
Provides an internal fixed speed command value. In bipolar mode, direction is
commanded by the sign of the reference.
98
TB Man Ref Lo
Range:
-/+Maximum Speed [0.1 Hz or 0.01 RPM]
Default:
0.0
Access:
1
Path:
Speed Command>Speed References
See also:
79, 96
99
Pulse Input Ref
Range:
-/+ 400.0 Hz or -/+ 24000.0RPM [0.1 Hz or 0.1 RPM]
Default:
Read Only
Access:
0
Path:
Speed Command>Speed References
See also:
100
Jog Speed 1
Range:
+/- Maximum Speed [0.1 Hz or 0.1 RPM]
Default:
10.0 Hz or 300.0 RPM
Access:
0
Path:
Speed Command>Discrete Speeds
See also:
79
101
102
103
104
105
106
107
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
Range:
-/+Maximum Speed [0.1 Hz or 1 RPM]
Default:
See table 3.1
Access:
See table 3.1
Path:
Speed Command>Discrete Speeds
See also:
79, 90, 93