3-98
DBT Reach Drive User Manual
46 = Run w/Comm:
Allows the comm start bit to operate like a run with the run input
on the terminal block. Ownership rules apply.
47 = Hold Step:
Inhibits profile from transitioning to next step when active.
48 = Set Home:
The input establishes the “home” position in speed profiling.
49 = Find Home:
Starts the commissioning procedure when a start command is
issued to automatically position the motor to a home position established by a limit
switch.
50 = Home Limit:
This input is used for the “home” position.
51 = Vel Override:
When active, multiplies value of Step X Velocity by % value in Vel
Override.
52-56 = Pos Sel 1-5:
The binary value of these inputs is used to select the starting
step number for the profile.
57 = Prof Input:
(Profile Input) Must be chosen if Step X Type is set to Dig Input and
the digital input value that is entered in Step X Value is the value of this digital input
selector.
Type 2 Alarms
Some digital input programming may cause conflicts that result in a Type 2 alarm. For
example, Digital In1 Sel set to 5 (Start) in 3-wire control, and Digital In2 Sel set to 7
(Run) in 2-wire control.
Sets the analog output value from a communication device.
Example: Set Data ln Ax (300-201) to 377 (value from communication device). Then
set Analog Outx Sel (342, 345) to 24 = Param Cntl.
377
378
Anlg1 Out Setpt
Anlg2 Out Setpt
Range:
0.000 to 20.000 mA or -/+10.000 V [0.001 mA or 0.001 V]
Default:
20.000 mA or 10.000 V
Access:
2
Path:
Inputs & Outputs>Analog Outputs
See also: