3-18
Programming and Parameters
Advanced Program Group
(continued)
Stop drive before changing this parameter.
A082 [DB Resistor Sel]
Enables/disables external dynamic braking.
Values
Default
0
Min/Max:
0/99
Display:
1
Setting
Min/Max
0
1
2
3-99
Disabled
AB Resistor (5% Duty Cycle)
No Protection (100% Duty Cycle)
Duty Cycle Limited (3% – 99% of Duty Cycle)
A083 [S Curve %]
Sets the percentage of acceleration or deceleration time that is applied to the ramp as S Curve. Time
is added, 1/2 at the beginning and 1/2 at the end of the ramp.
Values
Default
0% (Disabled)
Min/Max:
0/100%
Display:
1%
Example:
Accel Time = 10 Seconds
S Curve Setting = 30%
S Curve Time = 10
×
0.3 = 3 Seconds
S Curve Time = Accel Time
Total Time to Accelerate = Accel Time + S Curve Time
100% S Curve
Target
S Curve Time
Total Time to Accelerate = Accel Time + S Curve Time
50% S Curve
Target
Target/2
userman.book Page 18 Friday, June 21, 2002 2:48 PM
Summary of Contents for Allen-Bradley PowerFlex 4
Page 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Page 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Page 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Page 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Page 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Page 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Page 93: ...userman book Page 1 Friday June 21 2002 2 48 PM ...