Installation/Wiring
1-13
Figure 1.5 Control Wiring Block Diagram
No.
Signal
Default
Description
Param.
R1
Relay N.O.
Fault
Normally open contact for output relay.
R2
Relay Common
–
Common for output relay.
R3
Relay N.C.
Fault
Normally closed contact for output relay.
Sink/Source DIP Switch
Source (SRC)
Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch
setting.
01
Stop
(1)
Coast
The factory installed jumper or a normally closed input
must be present for the drive to start.
(1)
02
Start/Run FWD
Not Active
Command comes from the integral keypad by default. To
disable reverse operation, see A095 [Reverse Disable].
03
Direction/Run REV
Not Active
04
Digital Common
–
For digital inputs. Electronically isolated with digital inputs
from analog I/O.
05
Digital Input 1
Preset Frequencies Program with A051 [Digital In1 Sel].
06
Digital Input 2
Preset Frequencies Program with A052 [Digital In2 Sel].
11
+24V DC
–
Drive supplied power for digital inputs.
Maximum output current is 100mA.
12
+10V DC
–
Drive supplied power for 0-10V external potentiometer.
Maximum output current is 15mA.
13
0-10V In
(3)
Not Active
For external 0-10V input supply
(input impedance = 100k ohm) or potentiometer wiper.
14
Analog Common
–
For 0-10V In or 4-20mA In. Electronically isolated with
analog inputs from digital I/O.
15
4-20mA In
Not Active
For external 4-20mA input supply
(input impedance = 250 ohm).
16
RS485 (DSI) Shield
–
Terminal should be connected to safety ground - PE
when using the RS485 (DSI) communications port.
(3)
Only one analog frequency source may be connected at a time. If more than one reference is connected at the same
time, an undetermined frequency reference will result.
01
02
03
04
05
06
11
12
13
14
15
16
Stop
(1)
Start/Run FWD
(2)
Direction/Run REV
Digital Common
Digital Input 1
Digital Input 2
R1
R2
R3
Relay N.O.
Relay Common
Relay N.C.
+24V DC
+10V DC
0-10V In
Analog Common
4-20mA In
RS485 Shield
+24V
+10V
SRC
SNK
Typical
SNK Wiring
Typical
SRC Wiring
1
RS485
(DSI)
R1 R2 R3
01
02
03
04
05
06
11
12
13
14
15
16
SNK
SRC
(1)
Potentiometer
must be
1-10k ohm
2 Watt Min.
30V DC 125V AC 240V AC
Resistive
3.0A
3.0A
3.0A
Inductive
0.5A
0.5A
0.5A
(1)
Important:
I/O Terminal 01 is
always a coast to stop input except
when P036 [Start Source] is set to
“3-Wire” control. In three wire
control, I/O Terminal 01 is controlled
by P037 [Stop Mode]. All other stop
sources are controlled by P037
[Stop Mode].
Important:
The drive is shipped with
a jumper installed between I/O
Terminals 01 and 11. Remove this
jumper when using I/O Terminal 01
as a stop input.
(2)
Two wire control shown. For three
wire control use a momentary input
on I/O Terminal 02 to
command a start. Use a maintained
input
for I/O Terminal 03 to
change direction.
P036
[Start Source]
Stop
I/O Terminal 01
Stop
Keypad
Per P037
Coast
3-Wire
Per P037
Per P037
2-Wire
Per P037
Coast
RS485 Port
Per P037
Coast
userman.book Page 13 Friday, June 21, 2002 2:48 PM
Summary of Contents for Allen-Bradley PowerFlex 4
Page 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Page 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Page 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Page 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Page 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Page 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Page 93: ...userman book Page 1 Friday June 21 2002 2 48 PM ...