Installation/Wiring
1-7
Table 1.D Minimum Recommended Branch Circuit Protective Devices
Voltage
Rating
Drive Rating
kW (HP)
Fuse Rating
(1)
Amps
(1)
Recommended Fuse Type: UL Class J, CC, T or Type BS88; 600V (550V) or
equivalent.
140M Motor
Protectors
Catalog No.
Recommended
MCS Contactors
Catalog No.
120V AC –
1-Phase
0.2 (0.25)
0.37 (0.5)
0.75 (1.0)
10
15
30
140M-C2E-C10
140M-C2E-C16
140M-D8E-C20
100-C09
100-C12
100-C23
240V AC –
1-Phase
0.2 (0.25)
0.37 (0.5)
0.75 (1.0)
1.5 (2.0)
10
10
15
30
140M-C2E-B63
140M-C2E-B63
140M-C2E-C16
140M-D8E-C20
100-C09
100-C09
100-C12
100-C23
240V AC –
3-Phase
0.2 (0.25)
0.37 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
3
6
10
15
25
35
140M-C2E-B25
140M-C2E-B40
140M-C2E-C10
140M-C2E-C16
140M-C2E-C16
140M-F8E-C25
100-C09
100-C09
100-C09
100-C12
100-C16
100-C23
480V AC –
3-Phase
0.37 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
3
6
10
15
15
140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C10
140M-C2E-C16
100-C09
100-C09
100-C09
100-C09
100-C16
userman.book Page 7 Friday, June 21, 2002 2:48 PM
Summary of Contents for Allen-Bradley PowerFlex 4
Page 4: ...soc 2 userman book Page 2 Friday June 21 2002 2 48 PM ...
Page 6: ...ii userman book Page ii Friday June 21 2002 2 48 PM ...
Page 32: ...1 22 Installation Wiring Notes userman book Page 22 Friday June 21 2002 2 48 PM ...
Page 70: ...4 8 Troubleshooting Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 74: ...A 4 Supplemental Drive Information Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Page 82: ...B 8 Accessories and Dimensions Notes userman book Page 8 Friday June 21 2002 2 48 PM ...
Page 88: ...C 6 RS485 DSI Protocol Notes userman book Page 6 Friday June 21 2002 2 48 PM ...
Page 92: ...Index 4 Notes userman book Page 4 Friday June 21 2002 2 48 PM ...
Page 93: ...userman book Page 1 Friday June 21 2002 2 48 PM ...