16
Rockwell Automation Publication 440G-UM001B-EN-P - May 2016
Chapter 3
Installation and Wiring
Mounting
The Access Box can be mounted on hinged or sliding doors. The use of the
mounting plates is optional.
Figure 1 - Installation Example for Guard Door That Is Hinged on the Right
ATTENTION:
With two-wing hinged guard doors, one of the two guard door
wings must also be latched mechanically.
4x M6
2x M6
0.5 Nm
1 Nm (6x)
Cutout for Escape Release
IMPORTANT
Be careful when mounting the lock module cover to avoid pinching the
ribbon cable.
TIP
For easier installation, it is recommended that the handle assembly is
mounted to the guard door before the silver handle is attached to the
handle assembly.
IMPORTANT
It must be possible to insert the bolt tongue in the locking module. To check,
close the safety guard several times and actuate the guard door handle.
If available, check the function of the escape release. It must be possible to
operate the escape release from the inside without excessive force
(approximately 40
N).
ATTENTION:
The escape release must ONLY be accessible from inside the
safeguarded area. The installation must not allow access to the escape
release from outside the safeguarded area.