Rockwell Automation Publication 2198-IN001D-EN-P - February 2016

3

Kinetix 5500 Servo Drives

Remove the Grounding Screws

Grounding Screw Configurations

Install the Kinetix 5500 Servo Drive

These procedures assume that you have prepared your panel and understand how to bond your system. For installation instructions regarding 
equipment and accessories not included here, refer to the instructions that came with those products.

ATTENTION: 

To avoid personal injury, the grounding screws access door must be kept closed when power is applied. If power was present and then removed, 

wait at least 5 minutes for the DC-bus voltage to dissipate and verify that no DC-bus voltage exists before accessing the grounding screws.

ATTENTION: 

Risk of equipment damage exists. The drive ground configuration must be accurately determined. Leave the grounding screws installed for 

grounded power configurations (default). Remove the screws for ungrounded, ungrounded, corner-grounded, and impedance-grounded power.

Ground Configuration 

(1)

(1)

Refer to the Kinetix 5500 Servo Drives User Manual, publication

 2198-UM001

, for example configurations.

Grounding Screw Configuration

Benefits of Configuration

Grounded (wye)

Both screws installed (default setting)

• UL  and  EMC  compliance
• Reduced electrical noise
• Most stable operation
• Reduced voltage stress on components and motor bearings

• AC fed ungrounded
• Corner grounded
• Impedance grounded

Both screws removed

• Helps avoid severe equipment damage when ground faults occurs
• Reduced leakage current

Single-phase input power

AC screw removed 

(2)

(2)

Removing the AC grounding screw to minimize leakage current in single-phase operation can affect EMC performance.

Minimizes leakage current for single-phase operation

SHOCK HAZARD: 

To avoid hazard of electrical shock, perform all mounting and wiring of the Kinetix 5500 drive prior to applying power. Once power is applied, 

connector terminals can have voltage present even when not in use.

ATTENTION: 

Plan the installation of your system so that you can perform all cutting, drilling, tapping, and welding with the system removed from the enclosure. 

Because the system is of the open type construction, be careful to keep any metal debris from falling into it. Metal debris or other foreign matter can become 
lodged in the circuitry and result in damage to components.

Grounding screws are installed for grounded power configurations
(screws installed is default setting).
• Remove both screws for ungrounded, corner-grounded, and

impedance-grounded power for three-phase operation

• Remove only the AC screw for single-phase operation

Grounding Screw 
Access Door

Kinetix 5500 Drive 

(side view)

Lift door to meet 
arrow at left.

AC Screw
DC Screw

Summary of Contents for Allen-Bradley 2198-H***-ERS Series

Page 1: ...80 and GuardLogix 5570 or CompactLogix 5370 and Compact GuardLogix 5370 controllers Topic Page Summary of Changes 1 About the Kinetix 5500 Drives 1 Catalog Number Explanation 2 Before You Begin 2 Remo...

Page 2: ...r impedance grounded power configurations Removing the screws involves gaining access opening the side door and removing the screws Removing the grounding screws in multi axis configurations is best d...

Page 3: ...mpliance Reduced electrical noise Most stable operation Reduced voltage stress on components and motor bearings AC fed ungrounded Corner grounded Impedance grounded Both screws removed Helps avoid sev...

Page 4: ...n Refer to the Kinetix Servo Drives Technical Data publication GMC TD003 for Kinetix 5500 drive dimensions In multi axis shared bus configurations drives must be spaced by aligning the zero stack tab...

Page 5: ...at No Frame A mm in B mm in C mm in D mm in E mm in Drill Hole Patterns F mm in G mm in 2198 H003 ERSx 1 50 1 97 170 6 69 200 7 87 226 8 90 215 8 46 193 68 7 62 4 51 0 18 2198 H008 ERSx 2198 H015 ERSx...

Page 6: ...13 Link Activity status indicators 20 24V control input power CP connector 7 Zero stack mounting tab cutout 14 Motor power MP connector 21 Safe torque off STO connector 3 applies to only 2198 Hxxx ERS...

Page 7: ...2 DC DC Pin Description Signal 1 DC bus connections DC 2 DC CP Pin Description Signal 1 24V power supply customer supplied 24V 2 24V common 24V MP Pin Description Signal Color U Three phase motorpowe...

Page 8: ...put 1 This is a dual function input IN1 1 1 This signal has dual functionality You can use IN1 IOD 1 as registration or Home input 2 I O common for customer supplied 24V supply COM 3 24V current sinki...

Page 9: ...icalData publication KNX TD004 for cable specifications 8 0 0 31 0 5 0 6 4 4 5 3 2198 H070 ERSx 2 5 6 4 14 10 10 0 0 39 0 5 0 8 4 4 7 1 2198 Hxxx ERSx PELV SELV 24V power single axis CP connector CP 1...

Page 10: ...is Motor Cable Shield Clamp 2198 KITCON DSL Motor Feedback Connector Kit Motor Power MP Connector Motor Brake BC Connector Exposed shield braid under clamp Feedback cable routed around the shield clam...

Page 11: ...attaching the motor power brake shield clamp IMPORTANT If the power brake cableshield has a loose fit inside the shield clamp insert theclamp spacer between the shield clamp and the drive to reduce t...

Page 12: ...ications Drive Cat No Drive Voltage nom Phase Bussmann Fuses Cat No Molded Case CB Cat No DIN gG Fuses Amps max Molded Case CB Cat No 2198 H003 ERSx 240V Single phase KTK R 2 140U D6D2 B10 2 140U D6D2...

Page 13: ...SP 140G G6C3 C40 35 140G G6C3 C40 Kinetix 5500 Drive Cat No Drive Voltage three phase nom Bussmann Fuses Cat No Molded Case CB Cat No 2 Axes 3 Axes 4 Axes 5 Axes 2 Axes 3 Axes 4 Axes 5 Axes 2198 H003...

Page 14: ...meets the following UL requirements for solid state overload protection Refer to your servo drive user manual for the interconnect diagram that illustrates the wiring between your motor and drive Kin...

Page 15: ...hnical Data publication KNX TD004 Provides product specifications for Bulletin 2090 motor and interface cables low profile connector kits drive power components and other servo drive accessory items K...

Page 16: ...your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents...

Reviews: