Publication 1734-UM001D-EN-P - April 2008
Troubleshoot with the Indicators
163
Indication
Probable Cause
Recommended Action
Network Activity
Off
No link established.
Verify network cabling, and correct, as
needed.
Flashing
green/Off
Transmit or receive activity present.
None.
Steady green
Link established.
None.
Network Status
Off
Device not initialized. The module does not have an IP address.
Apply power to device, verify IP address,
and correct, as needed.
Flashing green
No CIP connections present. Device has an IP address, but no CIP
connections are established.
None.
Solid green
CIP connections present. Device online and has an IP address, and CIP
connections are established.
None.
Flashing red
One or more CIP connections has timed-out.
Check for I/O module failure and controller
operation, and correct, as needed.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as
needed.
Flashing
red/green
The module is performing a self-test (only occurs during power cycle
test).
None.
Summary of Contents for 1734-IA2
Page 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Page 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Page 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Page 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Page 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Page 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Page 241: ......