Publication 1734-UM001D-EN-P - April 2008
202
Configure POINT I/O Modules in RSLogix 5000 Software
You see the Low Value dialog.
6.
From the Low Value dialog, click Next to start calibration.
You see the High Value dialog.
7.
From the High Value dialog, click Next to start calibration.
You see the Calibration Completed dialog that shows you saved the
changed calibration constants of the channel.
Summary of Contents for 1734-IA2
Page 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Page 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Page 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Page 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Page 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Page 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Page 241: ......