Publication 1734-UM001D-EN-P - April 2008
Calibrate Your Analog Modules
127
Calibrate the Analog
Current Output Module
To calibrate your output module, connect the module in a DeviceNet system
similar to that shown in the figure, and use this procedure.
.
1.
Double-click the icon to bring up the General parameter dialog.
IMPORTANT
Apply power to the power supply and module for at least 10
minutes before calibrating the module. This allows internal
temperatures to stabilize and reduces drift errors.
0
1
0
1
0
1
0
1
0
1
0
1
44032
Power Supply Voltage
DeviceNet Input
PDN OE2C
250
Ω
Current Meter
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
Summary of Contents for 1734-IA2
Page 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Page 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Page 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Page 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Page 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Page 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Page 241: ......