Publication 1734-UM001D-EN-P - April 2008
Troubleshoot with the Indicators
157
1734-ACNR ControlNet Adapter
Module
Status
PointBus
Status
ControlNet A
Status
1734-ACNR
ControlNet B
Status
Field
Power
System
Power
A
B
0 2
System Power
Field Power
43265
Module Status
POINTBus Status
ControlNet A Status
ControlNet B Status
Indication
Probable Cause
Recommended Action
Module Status
Off
No power applied to device.
Apply power to device.
Alternating
red/green
LED power cycle test (module self-test) is present.
None.
Flashing red
Recoverable fault has occurred:
•
Firmware (NVS) update
•
MAC ID changed
•
CPU load exceeded
•
Complete firmware update.
•
Return module to correct node address.
•
Reduce CPU load.
Solid red
Unrecoverable fault has occurred:
•
Self test failure (checksum failure at power cycle
•
Ramtest failure at power cycle)
•
Firmware fatal error
Replace 1734-ACNR adapter.
Flashing green
Waiting for connection or ControlNet cable break.
Check cable and make connection, as needed.
Solid green
Module is operating correctly (normal mode).
None.
Summary of Contents for 1734-IA2
Page 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Page 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Page 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Page 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Page 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Page 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Page 241: ......