Calibrate Your Analog Modules
125
6.
Click the Download to Device button.
Both channel status indicators turn off.
7.
Click Calibration Channel Set to bring up channel selections, and select a
channel.
8.
Click the Download to Device button.
9.
Apply 4.00 mA to the input.
10.
Click Accept Low Calibration.
Leave on single.