Calibrate Your Analog Modules
139
10.
Enter the value shown on your DVM for the Channel Low Value
(-10.1234 in the example).
11.
Select the Output High Value and download to the module.
12.
Enter the value shown on the DVM onto your dialogs (10.0057 in this
example).
13.
Repeat these steps for the other channel.
Type in the
resulting value
from your DVM.
Type in the
resulting value
from your
DVM.