Publication 1734-UM001D-EN-P - April 2008
118
POINT I/O Module Data
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s
memory.
The 1734D-IB8XOB8E
module produces one byte of input data (scanner Rx)
status. It consumes one byte of output data (scanner Tx).
ATTENTION
Whatever field power you supply is connected to the
internal field-power bus. For example, if 120V ac is applied
to the power connections, there will be 120V ac applied to
the modules through the internal field-power bus.
POINT I/O modules to the right of the module will also
have that internal power bus voltage applied, unless you use
a 1734-FPD, 1734-EP24DC, or 1734-EPAC module to
interrupt and change the field power-bus voltage.
Default Data Map for the 1734D-IB8XOB8E dc Input/Output Module
Message Size: 1 Byte
7
6
5
4
3
2
1
0
Produces
(scanner Rx)
Ch7
Ch6
Ch5
Ch4
Ch3
Ch2
Ch1
Ch0
Input Data
Where:0 = off, 1 = on
Message Size: 1 Byte
CH
SH
24
CL
RT
En
CH
CL
GND
5V
DeviceNet
Connector
POINTBus
Expansion
Port
Field Bus
Connector
24V
to 5V
Microprocessor
I/O Circuits
I/O Connections
Power
Connections
41971
120V ac or 24V dc
Summary of Contents for 1734-IA2
Page 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Page 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Page 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Page 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Page 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Page 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Page 241: ......