1 Features and technical data
Installation, Use and Maintenance Manual – GAHP-A
17
GAHP-A HT STD
GAHP-A HT S1
Electrical power absorption
nominal
kW
0,84 (5)
0,77 (5)
minimum
kW
-
0,50 (5)
Degree of protection
IP
X5D
INSTALLATION DATA
gas consumption
methane G20 (nominal)
m3/h
2,72 (3)
methane G20 (min)
m3/h
1,34
G25 (nominal)
m3/h
3,16 (9)
G25 (min)
m3/h
1,57
G27 (nominal)
m3/h
3,32 (12)
G27 (min)
m3/h
1,62
G30 (nominal)
kg/h
2,03 (4)
G30 (min)
kg/h
0,99
G31 (nominal)
kg/h
2,00 (4)
G31 (min)
kg/h
0,98
NOx emission class
5
NOx emission
ppm
25
CO emission
ppm
36
Sound power Lw (max)
dB(A)
79,6 (8)
74 (8)
Sound power Lw (min)
dB(A)
-
71 (8)
Sound pressure Lp at 5 metres (max)
dB(A)
57,6 (10)
52 (10)
Sound pressure Lp at 5 metres (min)
dB(A)
-
49 (10)
Minimum storage temperature
°C
-30
Maximum water pressure in operation
bar
4
Maximum flow flue condensate
l/h
4
Water content inside the apparatus
l
4
Water fitting
TYPE
F
thread
" G
1 1/4
Gas connection
TYPE
F
thread
" G
3/4
Fume outlet
Diameter (∅)
mm
80
Residual head
Pa
80
Dimensions
width
mm
848 (6)
depth
mm
1258
height
mm
1281 (6)
1537 (6)
Weight
In operation
kg
390
400
Required air flow
m3/h
11000
Fan residual head
Pa
40
GENERAL INFORMATION
INSTALLATION MODE
B23P, B33, B53P
REFRIGERANT FLUID
AMMONIA R717
kg
7
WATER H2O
kg
10
MAXIMUM PRESSURE OF THE REFRIGERANT CIRCUIT
bar
32
Note:
(1) As per standard EN12309-2
(2) For flows other than nominal see Design Manual
(3) PCI (G20) 34,02 MJ/m3 (1013 mbar 15 °C).
(4) PCI (G30/G31) 46.34 MJ/kg (1013 mbar 15 °C).
(5) ± 10% according to the power supply voltage and tolerance on electrical motors consumption.
(6) Overall dimensions without flue gas exhaust ducts.
(7) A special version is available as optional feature for operation at -30 °C.
(8) Sound power values detected in compliance with the intensity measurement methodology set forth by standard EN ISO 9614.
(9) PCI (G25) 29,25 MJ/m3 (1013 mbar 15 °C).
(10) Maximum sound pressure levels in free field, with directionality factor 2, obtained from the sound power level in compliance with standard EN ISO 9614.
(11) Under transitory conditions lower temperatures are allowed.
(12) PCI (G27) 27,89 MJ/m3 (1013 mbar 15 °C).