6
Note that in England and Wales the Building Regulations require a terminal guard to be fitted if the terminal is less than 2m
(6ft 6in) from the level of any ground, balcony, flat roof or place to which any person has access and which adjoins the wall
in which the outlet is situated. A suitable guard assembly is available from Robinson Willey Limited. The part number is
994371. In Scotland, although the Building Standards (Scotland) do not require a terminal guard to be fitted, the fitting of a
guard as detailed above is recommended.
INSIDE CLEARANCES :
1. Allow 50mm access at each side of the heater for servicing.
2. Curtains must be 150mm clear at the top of the heater and 50mm at the sides and must not be closeable over the front
of the heater.
3. A wooden or combustible shelf may be fitted over the heater. The minimum height of the underside of the shelf of
125mm depth must be 130mm . For shelves of greater depth, allow an additional clearance of 15mm for every 25mm
additional shelf depth.
4. A minimum clearance to combustible material of 500mm is required around the heater.
6.1 Siting The Heater
Outside (Fig. 3): Check that the terminal location complies with the requirements of the table below.
TERMINAL POSITION
MINIMUM DISTANCE
A -
Directly below an openable window or other opening e.g. air brick
300mm
B -
Below gutters, soil pipes or drain pipes
300mm
C -
Below eaves
300mm
D -
Below balconies or car port roof
600mm
E -
From vertical soil pipes or drain pipes
75mm
F
-
From internal or external corners
600mm
G -
Above ground, roof or balcony level
300mm
H -
From a surface facing a terminal
600mm
I
-
From a terminal facing a terminal
600mm
J
-
From an opening in the car port (e.g. door, window) into dwelling
1200mm
K -
Vertically from a terminal on the same wall
1500mm
L
-
Horizontally from a terminal on the same wall
300mm
B C
F
A
G
E
H
J
G
A
F
K L
L
K
Fig. 3