Robinson Willey ATHENA R.S. Installation And Servicing Instructions Download Page 10

10

10.0 PREPARATION OF HEATER

10.1

Remove Outer Case (Fig 9.)

(a) Remove the outer case by lifting it up and away from the locating hooks.

(b) Remove the tensioning bolt mounting bracket from the underside of the combustion box. This is done by removing the 

two fixing screws. Take care not to damage the wires of the ignition unit as this is attached to the same bracket.

10.2

Fit Flue

(a) Place the heater face down taking care to protect any soft surface.

(b) Fit the flue and air ducts to the back of the heater using the gaskets and screws provided. This operation is made 

easier by using the screws to tap the holes before assembly. The four screws for the flue duct are already fitted to the 

heater. The flanges of the ducts are marked ‘TOP’ to indicate the way in which the ducts are to be fitted. Note: 

DO NOT

 

remove the two middle slotted screws.

Fig. 6A

ADJUST FLUE

LENGTH TO

SUIT WALL

THICKNESS

134mm

SCREWS

FLUE DUCT

SEALING TAPE

FOAM

SEALING STRIP

FLUE TERMINAL

12

5m

m

 D

IA

.

‘A’

‘A’

INNER AIR DUCT

INNER AIR DUCT

SCREW

SCREW

TERMINAL

TERMINAL

SEALING TAPE

SEALING TAPE

Fig. 6B

(c) Adjust the flue length: First measure the wall thickness to give the overall length of flue ‘A’. Fit the terminal assembly to 

the ducts already fitted to the heater. The top of the assembly is marked ‘TOP’. Set the overall length of the flue to the 

dimension ‘A’ (Fig. 6A). Drill 2.7 mm diameter for the fixing screws and secure it with the screws provided. Seal the joint 

using the self-adhesive tape provided.

IMPORTANT NOTES:

(i) If rear entry gas supply connection is required, then it 

MUST

 be installed prior to the installation of the 

heater into the wall (see Section 11.1 Rear Entry Gas Connection).

(ii) If front entry gas supply connection from the left or right side is required, then it 

MUST

 be installed after the 

installation of the heater into the wall (see Section 11.2 Front Entry Gas Connection).

(iii) A suitable means of isolation must be fitted in the gas supply line to the heater.

(e) To insert the fixing cables it is necessary to remove the lower air guide. This is done by removing the two fixing screws 

and sliding it out (see Fig 4.). 

(f) Insert the free end of the cables through the respective holes in the back panel of the heater, and then down through 

the cable fixing eyelets. The cables are then inserted through the lower holes in the back panel of the heater and 

through the holes in the tensioning bolts. Re-fit the tensioning bolt mounting bracket.

(g) Remove the tape from the foam sealing strip on the terminal. Do not remove the tape before the heater is ready to be 

installed as the foam strip commences to expand once the tape is removed. The rate of expansion however, is low and 

there will be adequate time to install the heater, after which the foam strip will continue to expand and fill the gap 

between the flue and the wall. If for any reason the sealing strip has already expanded before the heater is installed, it 

can simply be compressed by hand until it is flush with the surface of the flue.

Fig. 6C

Summary of Contents for ATHENA R.S.

Page 1: ...INSTALLATION Installation and Servicing Instructions Room Sealed Inset Live Fuel Effect Gas Fire PRODUCT No A99009 G C No 32 170 17 CE MARKED FOR USE IN G B I E LEAVE THESE INSTRUCTIONS WITH THE USER...

Page 2: ...ION 5 3 FLUE TERMINAL LOCATION 6 4 CABLE FIXING 7 5 FLUE ASSEMBLY IN TIMBER FRAMED AND COMBUSTIBLE CONSTRUCTION 9 6A OVERALL FLUE LENGTH 10 6B FLUE ASSEMBLY INSTALLED 10 6C EXPLODED DIAGRAM OF FLUE CO...

Page 3: ...extras are available Part No Combustible Wall Kit 994530 Terminal Guard 994371 Gas Safety Installation and Use Regulations 1994 as amended It is the law that all gas appliances are installed by compe...

Page 4: ...ting type and if damaged must be replaced with the proper spare see Section 16 0 Short List of Parts 4 8 WARNING Do not operate appliance with the glass front removed cracked or broken 4 9 WARNING Do...

Page 5: ...0 C application i e marked withthe suffix 150 If it is not feasible to cut anopening in the wallthen a rebated surroundwith a 152 mmrebate should be used to enable the heaterto be fixed to the inner f...

Page 6: ...ight of the underside of the shelf of 125mm depth must be 130mm For shelves of greater depth allow an additional clearance of 15mm for every 25mm additional shelf depth 4 A minimum clearance to combus...

Page 7: ...suring that the wall above the opening is properly supported using the appropriate lintel see Section 13 0 Guidance on Fitting a Lintel 7 2 Position the template supplied on the inner face of the oute...

Page 8: ...anges of the ducts are marked TOP to indicate the way in which the ducts are to be fitted Note DO NOT remove the two middle slotted screws 8 8 Adjust the flue length First measure the wall thickness a...

Page 9: ...cut the hole 135 mm diameter making allowances for the shrinkage of the timber frame d Measure the thickness of the combustible part of the wall and cut the flue liner to this length cutting off the e...

Page 10: ...th the screws provided Seal the joint using the self adhesive tape provided IMPORTANT NOTES i If rear entry gas supply connection is required then it MUST be installed prior to the installation of the...

Page 11: ...ensioning bolts j Re fit the lower air guide ensuring that the long edge with the flange points down and rests on top of the first heat exchanger g If a terminal guard is required optional extra No 99...

Page 12: ...ove the pressure test point sealing screw and connect a pressure gauge to the test point a Light the heater Please refer to the Users Instructions Slide the control knob to the full on position marked...

Page 13: ...heater is required see Fig 10 If there are no existingopenings or beams withineither triangle proceed withforming the opening However if openings or beams occurwithin either triangle either 1 Use the...

Page 14: ...see Fig 12 13 5 Remove the masonry below the lintel and clear all the debris from the cavity Construct the opening to the size specified in Section 7 0 Non Combustible Wall Installation see Fig 4 A Ro...

Page 15: ...curing screws and remove the control knob d Remove the four infill frame securing screws and remove the infill frame e Remove the lower air guide Fig 4 f Remove the Right hand side air guide g Refitti...

Page 16: ...burner support plate in position Fig 19 g Remove the burner by sliding it towards the right 1 and then lift the left end of the burner upwards 2 see Fig 18 The burner can now be withdrawn through the...

Page 17: ...t the yellow interrupt wires from the thermocouple b Remove the thermocouple from the bottom of the slider control FSD c Remove the thermocouple from the pilot d Refitting is the reverse procedure of...

Page 18: ...everse procedure of removal 14 14 Removing The Thermocouple Break Micro switch a Remove the outer case as previously described in Section 14 1 b Disconnect the yellow wires from the thermocouple break...

Reviews: