Page 63
CABINET HEATER
9.4
Solenoid Valve Circuit
To test the operation of a solenoid valve requires the checking of both the electrical and the mechanical operations.
To test the mechanical operation of the valve requires a suitable pressure gauge to be fitted to the outlet of the valve
and the rise in pressure observed at the appropriate time.
YES
Is there pressure on the outlet of the
valve when the valve
should be closed ?
Is there an electrical supply to the
valve terminals ?
YES
Fault lies elsewhere.
Investigate and correct.
Valve faulty.
Replace with correct type.
Does valve open at the correct time
?
Is there an electrical supply to the
valve terminals ?
Fault lies elsewhere.
Investigate and correct.
Valve faulty.
Replace with correct type.
VALVE OPERATING
NO
NO
NO
NO
YES
YES