Page 59
CABINET HEATER
Section 9.
Fault Finding Charts
Following the replacement or adjustment of parts carry out the commissioning procedure as specified in Section 5 and
the burner manufacturers instructions.
General - All heaters
WARNING
FAULT FINDING SHOULD ONLY BE CARRIED OUT BY
EXPERIENCED ENGINEERS WHO FULLY UNDERSTAND THE
OPERATION OF THE BURNERS.
GAS HEATERS MAY ONLY BE REPAIRED BY A C.O.R.G.I.
REGISTERED ENGINEER.
THERE IS A RISK, INCLUDING THAT OF EXPLOSION, WHEN
BURNERS ARE FAULTY
AND NOT REPAIRED CORRECTLY.
START
Assuming fuel & electrical
supplies are ON
Does the burner fire ?
Is the 'lockout' button on
the burner alight ?
Check control fuse in
heater has not blown
Repair as necessary
Test burner as in
9.1 (oil fired)
9.2 (gas fired)
Check external controls
are ON and the fuse in the
burner is sound
Press in white button on
fan/limit
thermostat
Does the main fan run ?
Use 9.5 or 9.6 to test fan
See Section 5.1.2 to
check thermostat settings
Replace fan/limit
thermostat
Does the burner stop after
running for several
minutes with controls still
ON ?
Did burner 'lockout' ?
Check main fan for
blockage or belt tension
and correct rotation
Use 9.1 or 9.2 to test
burner
Check operation and
setting of fan/limit
thermostat.
Repair or replace as
necessary
HEATER OPERATING
NO
NO
NO
NO
NO
NO
YES
NO
NO
YES
YES
YES
YES
NO
YES
YES
Summary of Contents for Combat HF 30 v4
Page 2: ......
Page 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Page 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Page 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Page 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Page 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...