CABINET HEATER
Fig 2.2 Gas Fired Heater Control Box Sequence
2.3.3
Air Pressure Switch Contacts
The combustion air fan now turns on and the air pressure switch contacts (n.o.) have to close within the next 5
seconds to indicate the availability of sufficient combustion air or lockout will occur.
2.3.4
Purge
The sequence continues with a purge time with the burner fan only running.
2.3.5
Electric Ignition ON
The electric ignition switches ON at the end of this purge time.
2.3.6
Start Gas Valve (Main gas for models 015 to 030)
The start gas valve opens and once a flame has been established this remains on until close down. The flame probe is
now continuously monitoring for the safe presence of flame.
2.3.7
Electric Ignition OFF
Five seconds later the electric ignition turns off, leaving the start gas flame to be proved as stable.