Page 10
CABINET HEATER
Table 2.3
Oil Fired Burner Data (Ecoflam Burner)
Burner Reference "G"
DATA TABLES - IMPORTANT NOTE
When reading the Data Tables 2.3 to 2.9 on the following pages,
ensure that the correct table for the burner and gas valve installed is being used.
The Data Tables are listed under a burner reference letter which can be found
on the heater data plate.
Refer also to the Burner Manufacturer's Instructions
and the specific instructions supplement where applicable.
The burner settings shown in the instructions should be used for burner settings.
Note: High Flow Heaters are fitted with burners to the same specification as the POP 30, 40 and 50 models for oil firing.
M ode l
POP 015 POP 020
POP 030
POP 040
POP 050
POP 060
POP 070
POP 080
POP 0100
He at Input (gr os s )
Kw
51
73.6
109.7
146.2
183.2
221.2
256.2
300.6
355.8
Btu/hr
174012
251073
374277
498786
625000
754870
874060
1025647
1213874
Nom inal He at output
Kw
44
58.6
87.9
117.2
146.5
175.8
205.2
234.5
293.1
Btu/hr
150000
200000
300000
400000
500000
600000
700000
800000
1000000
Ecoflam Bur ne r type
Minor 8
Minor 8
Minor 12
Minor 20
Minor 20
Minor 30
Minor 30
Minor 30
Major 30
Noz zle Siz e
Us gall/hr 1.00 1.50 2.25 3.00 3.00 4.00 5.00 5.50 7.00
Angle & Type
60S 60S 60S 60S 60S 60A 60A 60A 60A
M ak e
Danf os s Danf os s Danf os s Danf os s Danf os s Delevan Delevan Delevan Delevan
He ad s e tting
mm 8 0 14
8
(Fully bac k)
8
(Fully bac k)
8
(Fully bac k)
8
(Fully back)
8
(Fully bac k)
(Fully
Forward)
Air s e tting
Number 4.2 8.5 5.5 2.5 4 3.7 4.5 6.2 1.8
Bur ne r fue l
Bar 12 10.3 10.3 10 13.8 12.4 10.7 10 11
pr e s s ur e
PSI 175 150 150 145 200 180 155 145 160
Fue l
L/hr
4.82
6.96
10.37
13.83
17.32
20.92
24.23
28.43
33.65
cons um ption
imp gall.hr
1.06
1.53
2.28
3
3.81
4.6
5.33
6.25
7.4
M ax. oil pr e s s ur e
Bar
0.21
0.21
0.21
0.21
0.21
0.21
0.21
0.21
0.21
to pum p inle t
PSI
3
3
3
3
3
3
3
3
3
Summary of Contents for Combat HF 30 v4
Page 2: ......
Page 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Page 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Page 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Page 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Page 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...