Page 61
CABINET HEATER
9.2
Gas Burner Fault Finding (see also Burner Manufacturer's Instructions)
Gas heaters may only be repaired by a C.O.R.G.I. registered engineer.
Start by assuming that there is a proven fuel and electricity supply to the burner i.e. all external controls are on.
Does the burner fan run ?
Is the air pressure switch
at rest
(no contact open)
See Section 5 for setting
Fault lies elsewhere
Does 'lockout' occur before the
burner has run for 10 secs ?
Use 9.3 to check the flame
monitoring system
Does 'lockout' occur after the
burner has run for 10 secs ?
Check settings
air pressure switches
Check combustion air fan is clean.
Check combustion chamber
is clean and sound.
Check flue is clean and sound.
Check joint between flue spigot and
flue is sound.
NO
NO
NO
NO
NO
YES
YES
YES
Does the burner fire ?
Check ignition circuit, fuel supply
and gas solenoid valves
Does 'lockout' occur ?
Use 9.3 to check flame monitoring
circuit
Does main gas fire ?
Check main gas valves and wiring
BURNER OPERATING
YES
YES
YES
YES
NO
NO
YES
YES
Summary of Contents for Combat HF 30 v4
Page 2: ......
Page 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Page 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Page 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Page 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Page 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...