Page 11
CABINET HEATER
Table 2.4
Ecoflam ON/OFF Natural Gas (G20) Dungs Valve, Burner
Reference C
Data for all versions "H" horizontal, "HF" high flow
Gas rates corrected to standard conditions 1013.25 mbar 15°C
HEAD SETTING
- See Adjustment Of The Firing Head in Ecoflam Instructions
INLET PRESSURE 20 m ba r
(Minim um 17 m ba r, M a x im um 25 m ba r)
M ODEL
PGP 015 PGP 020 PGP 030 PGP 040 PGP 050 PGP 060 PGP 070 PGP 080 PGP 0100
Gross heat input
(kW)
56.1
73.7
103
144.7
182.1
220
253.6
297
363
Net heat Input
(kW)
51
67
93.6
131.5
165.5
200
230.5
270
330
A pprox heat output
(kW)
46.9
60.3
81.9
114.7
144.8
176
202.8
237.6
290.1
Start Gas Orif ice
(mm dia.)
5.0
6.0
7.0
7.0
7.0
7.0
Max Gas Rate
(Sm
3
/hr)
5.4
7.1
9.9
13.9
17.5
21.2
24.4
28.6
34.9
Main Burner Gas Pres sure
(mbar)
4.7
2.5
4.9
5.2
8.5
5.6
7.5
9.5
11
Start Gas Pressure
(mbar)
N/A
N/A
N/A
1.8
2.8
0.9
1.1
1.7
3.4
BURNER TYPE
A ZUR
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
60
120
120
170
250R
250
250
250S
350
Burner Head
s
s
s
s
s
s
s
s
s
Burner Injec tor
Head Setting
(mm)
0
10
11
15
14
24
24
24
21
1s t Flame A ir Setting
3.5 3.9 8 2.8 5.1 3.3 5.3 2 2
2nd Flame A ir Setting
Gas V alve Setting
V alve Type
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
Main Gas
405
405
405
407
410
410
410
410
412
V alve Type
S
S
S
S
S
S
Start Gas
0 832 051 0 832 051 0 832 051 0 832 051 0 832 051 0 832 051
A IR PRESSURE SWITCH
SETTING (mbar)
3.8
4.5
5.9
2.9
5.5
3.6
4.5
6.8
5.1
Max f lue static pres sure
norm. f lue static pres sure
(mbar)
-0.05
-0.05
-0.09
-0.30
-0.05
-0.25
-0.17
0.10
0.45
Gas Connec tion
3/4"
3/4"
3/4"
3/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
S.= S.I T
H.= HONEY WELL
Summary of Contents for Combat HF 30 v4
Page 2: ......
Page 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Page 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Page 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Page 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Page 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...