Page 36
CABINET HEATER
Fig 4.1 B.M.Oil Lifter
Technical data
Maximum lift............... 8 metres
Maximum capacity...... 20 litres/hr
Actual capactity.......... 10 to 20 l/hr
Dependant upon vertical lift and suction line
length.
240V
Oil Lifter
Oil Heater
Storage Tank
Filler Pipe
Air Vent
Max.
3m
Min.
0.15m
Min.
0.15m
Max.
8m
Flow
Output
- Litres
per
Hour
Flow
Output
- Imperial
Gallons
per
Hour
33ft
65ft
99ft
132ft
165ft
Lift in Feet
Lift in Metres
Total Suction Length in Feet
8mm (
5
/
16
") O.D. Copper Tube
Fig. 4.2
Pressurised System Installation - Duplex System
(The system shown has one pump for run and the other for stand by. The valves allow the stand by pump to be
removed for maintenance whilst the system is still running).
Check
Valve
Check
Valve
Stop
Valve
Stop
Valve
Stop
Valve
Stop
Valve
Check
Valve
Storage Tank below ground
For fuel
tanks
above
pump set
No.1
Pump
No.2
Pump
Relief Valve
Pressure Gauge
Pressure
Reducing
Valve
Burner
DUPLEX PUMP SET
Pressure
Reducing
Valve
Burner
Summary of Contents for Combat HF 30 v4
Page 2: ......
Page 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Page 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Page 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Page 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Page 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...