www.rletech.com
28
970.484.6510
3
Installation
Figure 3.3
Lower Right Terminal Block
Once the three wires are connected inside the terminal block, turn the AC power supply back
on. The LD5100 should begin booting up. Wait approximately one minute. No alarm should
be present.
On the LCD, press any key for the main menu. Enter the Cable Status menu. The cable length
is displayed. If this reading varies by more than ±5% of the actual length of cable installed,
verify the installation.
Through the LCD submenus, you may set the clock, system name, alarm configuration, feet/
meters, etc.
Wait at least 30 minutes before calibrating the LD5100. Calibrate the LD5100 through the
front panel System Setup menu.
Map the cable per the instructions in Chapter 6, “Mapping the Cable” on page 41.