www.rletech.com
25
970.484.6510
C
H A P T E R
C
HAPTER
0
I
NSTALLATION
3.1.
Installing the Unit
The LD5100 is a wall mounted device. To secure the device to the wall, first remove the
aluminum back panel and all electronics from the enclosure. There are knockouts on the top
and bottom of the enclosure designed to accommodate. 5 inch (12.7mm) conduit. Remove as
many as necessary. There are two holes in the top back of the unit spaced 11 inches (.28m)
apart. Use drywall anchors or suitable anchors depending on the wall construction, to secure
the unit to the wall. Put two more anchors through the two holes in the bottom back of the unit.
Reinstall the back panel and reconnect the electronics.
3.2.
Connecting the SeaHawk Water Leak Detection
Cable (SC)
The LD5100 requires a leader cable kit (part #LC-KIT; purchased separately) which includes
a 15 foot (4.57m) leader cable. One end of this leader cable connects into the LD5100. This
end of the cable has four stripped, bare wires. The other end features a mating connector which
connects with the Sea Hawk Leak Detection Cable (SC). The end of the cable is finished with
a removable end terminator (EOL).
Note
A Leader Cable Kit (part #LC-KIT) is required to connect the LD5100 to the SeaHawk Leak
Detection Cable (SC). The kits are not included with the LD5100 and can be purchased
separately.
Connect the 15 foot (4.57m) leader cable to the LD5100. From left to right, with the screws of
the terminal block connector facing up, the wires that screw into the terminal connector should
be colored white, black, green, and red. If the terminal connector is removed from the end of
the cable, make sure the wires are in this same order when the connector is reapplied.
Summary of Contents for LD5100
Page 1: ...Leak Detection LD5100 User Guide...
Page 8: ...970 484 6510 8 rletech com Notes...
Page 11: ...970 484 6510 11 rletech com...
Page 12: ...970 484 6510 12 rletech com Notes...
Page 14: ...970 484 6510 14 rletech com Notes...
Page 24: ...www rletech com 24 970 484 6510 2 Connections and Settings Notes...
Page 30: ...www rletech com 30 970 484 6510 4 4 20mA Output Testing Notes...
Page 48: ...www rletech com 48 970 484 6510 7 EIA 232 Interface Notes...
Page 60: ...www rletech com 60 970 484 6510 A Updating Firmware Notes...
Page 66: ...www rletech com 66 970 484 6510 C Preventive Maintenance Notes...
Page 70: ...www rletech com 70 970 484 6510 D Troubleshooting Notes...