www.rletech.com
35
970.484.6510
5
LCD Interface
5.5.
Alarm History/Trend Log
The
Alarm History/ Trend
Log Screen allows users to view the alarm history, trend log, and
erase data from both.
Figure 5.6
LD5100 Cable Status Screen
5.5.1 Alarm History Log
The Alarm History Log displays the most recent 100 events recorded by the unit. Events are
displayed in the following manner:
Date Time
Description
whereas
:
Date
is the date the event occurred.
Time
is the time at which the event occurred.
Description
is a detail of the nature of the event.
5.5.2 Trend Log
The Trend Log displays the leakage current on the cable. One measurement is taken at the user
set interval (1 min - 1440 min; factory default is 1440 min, or 1 day). The log retains the 288
most recent entries. Analyzing the trend data can help determine the location of long term
contamination build up, or degradation, on the cable.
5.5.3 Erase Alarm History
Erase Alarm History will clear all events log in the history table.
5.5.4 Erase Trend log
Erase Trend log will clear all trend data logged in the trend table.
Summary of Contents for LD5100
Page 1: ...Leak Detection LD5100 User Guide...
Page 8: ...970 484 6510 8 rletech com Notes...
Page 11: ...970 484 6510 11 rletech com...
Page 12: ...970 484 6510 12 rletech com Notes...
Page 14: ...970 484 6510 14 rletech com Notes...
Page 24: ...www rletech com 24 970 484 6510 2 Connections and Settings Notes...
Page 30: ...www rletech com 30 970 484 6510 4 4 20mA Output Testing Notes...
Page 48: ...www rletech com 48 970 484 6510 7 EIA 232 Interface Notes...
Page 60: ...www rletech com 60 970 484 6510 A Updating Firmware Notes...
Page 66: ...www rletech com 66 970 484 6510 C Preventive Maintenance Notes...
Page 70: ...www rletech com 70 970 484 6510 D Troubleshooting Notes...