www.rletech.com
42
970.484.6510
6
Mapping the Cable
6.1. Mapping
Directions
1
If a cable reference map (part #FM114) was not ordered from RLE Technologies, LD5100
users must create a drawing that represents the floor plan. This drawing must include the
room layout (walls, doors, and other permanent structures), the SC cable routing path, any
jumper sections of non-sensing cable (NSC) and any weighted cable connectors/simulators
(WCCS). Marking up a CAD drawing of the Facility works the best.
2
Physically identify points along the cable routing path. The points should be easily
accessible and evenly spaced. Number the points and record their location on the reference
map. Note where the connectors are located along the cable run.
3
Using the front panel of the LD5100, select
Point Mapping
and press
Enter
.
4
To test the map, wrap a wet paper towel or sponge or pour a small puddle of water around
the cable at one of the previously mapped points. The LD5100 produces a short beep within
approximately 30 seconds. The LCD displays the LD5100's calculated distance to the leak.
Remove the paper towel and dry the cable. Within approximately 20 seconds, the LD5100
produces a long beep indicating the short is removed and the system has returned to normal.
Tip
If the individual mapping the cable is not in a position to hear the audible alarm, wait two
minutes between each point. This ensures the system has had time to stabilize.
Loss of power or re-entering the Point Mapping menu will cause all mapping data
to be lost (reset).
5
When mapping is complete, press the
Left
arrow key on the LD5100 to exit the mapping
mode.
6
Select
View Map
on the LCD and record the LD5100's reading of each point on the
reference map.
7
Mount the cable reference map alongside to the LD5100 control panel or the remote
display. When a leak or cable break occurs, refer to the map and the distance displayed on
the LD5100 to determine the physical location of the leak.
W
ARNING
Summary of Contents for LD5100
Page 1: ...Leak Detection LD5100 User Guide...
Page 8: ...970 484 6510 8 rletech com Notes...
Page 11: ...970 484 6510 11 rletech com...
Page 12: ...970 484 6510 12 rletech com Notes...
Page 14: ...970 484 6510 14 rletech com Notes...
Page 24: ...www rletech com 24 970 484 6510 2 Connections and Settings Notes...
Page 30: ...www rletech com 30 970 484 6510 4 4 20mA Output Testing Notes...
Page 48: ...www rletech com 48 970 484 6510 7 EIA 232 Interface Notes...
Page 60: ...www rletech com 60 970 484 6510 A Updating Firmware Notes...
Page 66: ...www rletech com 66 970 484 6510 C Preventive Maintenance Notes...
Page 70: ...www rletech com 70 970 484 6510 D Troubleshooting Notes...