Table E.1
Technical Specifications
Power
100-240VAC @ 500mA Max, 50/60 Hz; hardwired power
supply
Inputs
Water Leak Detection Cable
Compatible with SeaHawk SC Cable (not included)
Cable Input
Requires SeaHawk LC-KIT: 15ft (4.57m) leader cable and
EOL (LC-KIT not included)
Maximum Length
5,000ft (1,524m)
Detection Accuracy
± 2ft (0.6m)+/- 0.5% of the cable length
Detection Repeatability
± 2ft (0.6m) +/- 0.25% of the cable length
Detection Response Time
5-990sec, software adjustable in 5sec increments; ±2sec
Outputs
Analog
4-20mA Loop Powered, 18-36VDC, RL = 500? max.
Relay
2 Form C Leak Relays, 2 Form C Cable Break Relays; 1A
@ 24VDC, 0.5A resistive @ 120VAC; configurable for
supervised or non-supervised, latched or non-latched
Communications Ports
RS-232
9600 baud; No parity, 8 data bits, 1 stop bit
RS-485
1200, 2400, 9600 or 19200 baud (selectable);
No parity, 8 data bits, 1 stop bit
Protocols
Modbus
(RS-485)
Slave; RTU Mode; Supports function codes 03, 04, 06 and
16
Terminal Emulation
(RS-232)
VT100 compatible
Alarm Notification
Audible Alarm
85DBA @ 2ft (0.6m); re-sound 0-999min
Summary of Contents for LD5100
Page 1: ...Leak Detection LD5100 User Guide...
Page 8: ...970 484 6510 8 rletech com Notes...
Page 11: ...970 484 6510 11 rletech com...
Page 12: ...970 484 6510 12 rletech com Notes...
Page 14: ...970 484 6510 14 rletech com Notes...
Page 24: ...www rletech com 24 970 484 6510 2 Connections and Settings Notes...
Page 30: ...www rletech com 30 970 484 6510 4 4 20mA Output Testing Notes...
Page 48: ...www rletech com 48 970 484 6510 7 EIA 232 Interface Notes...
Page 60: ...www rletech com 60 970 484 6510 A Updating Firmware Notes...
Page 66: ...www rletech com 66 970 484 6510 C Preventive Maintenance Notes...
Page 70: ...www rletech com 70 970 484 6510 D Troubleshooting Notes...