Connections and Settings
2.1.6 TB4 & TB5: Relays
Terminals TB4 and TB5 are Form C Relay Outputs. Each terminal has two outputs. TB4
provides a connection to one of the leak alarm relay outputs and one of the fault relay outputs;
TB5 provides a second set of contacts for the same leak and fault alarms.
The six contacts on TB4 and TB5 are labeled
Leak NO
,
Leak C
,
Leak NC
,
Fault NO
,
Fault
C
, and
Fault NC
. Connect the alarm relay wires to TB4 and TB5 as follows:
TB4-1 Leak alarm normally open (NO)
TB4-2 Leak alarm common (C)
TB4-3 Leak alarm normally closed (NC)
TB4-4 Fault alarm normally open (NO)
TB4-5 Fault alarm common (C)
TB4-6 Fault alarm normally closed (NC)
TB5-1 Leak alarm normally open (NO)
TB5-2 Leak alarm common (C)
TB5-3 Leak alarm normally closed (NC)
TB5-4 Fault alarm normally open (NO)
TB5-5 Fault alarm common (C)
TB5-6 Fault alarm normally closed (NC)
Two LEDs, labeled
K1Fault
and
K2Lea
k, are located above TB4 and TB5 in the LED status
strip near the center of the main board. They indicate the status of the relays On/Off. The leak
detection relay is activated when a leak is detected. The cable break relay is activated when a
cable fault is detected.
These relays are set to factory defaulted to Unsupervised; see 5.8.7, “Supervised Relays” on
page 37, for Supervised Relays function.
Both relays (all alarms) can be configured to be latched or unlatched. A latched alarm requires
a manual reset of the system once a leak or cable problem is no longer present.
2.1.7 RS232 Connector
The RS232 port uses only the transmit, receive, and ground pins (2, 3 and 5). The baud rate is
9600. The RS232 port is set to no parity, 8 databits, 1 stop bit (n, 8, 1). A straight through
cable should be used to connect a terminal or PC to the LD5100.
2.1.8 TB6: 4-20mA Output
A 4-20mA loop powered output is provided on TB6. The maximum range (20 mA) can be set
to 1000, 2500, or 5000 feet. Connect the 4-20mA wires to TB6 as follows:
TB6-1 4-20mA positive (+)
TB6-2 4-20mA negative (-)
Summary of Contents for LD5100
Page 1: ...Leak Detection LD5100 User Guide...
Page 8: ...970 484 6510 8 rletech com Notes...
Page 11: ...970 484 6510 11 rletech com...
Page 12: ...970 484 6510 12 rletech com Notes...
Page 14: ...970 484 6510 14 rletech com Notes...
Page 24: ...www rletech com 24 970 484 6510 2 Connections and Settings Notes...
Page 30: ...www rletech com 30 970 484 6510 4 4 20mA Output Testing Notes...
Page 48: ...www rletech com 48 970 484 6510 7 EIA 232 Interface Notes...
Page 60: ...www rletech com 60 970 484 6510 A Updating Firmware Notes...
Page 66: ...www rletech com 66 970 484 6510 C Preventive Maintenance Notes...
Page 70: ...www rletech com 70 970 484 6510 D Troubleshooting Notes...