www.rletech.com
63
970.484.6510
B
Leak Detection Modbus Master
B.3.
Configuring the LD5100 Via the EIA-232 (Craft)
Port
First, the Com Port Setting must be configured on the LD5100:
1
Using the Local display (LCD) on the LD5100 press any of the buttons. Move the cursor
down and select the Com Port Settings, press Enter to access the menu.
2
The cursor will be to the left of Port1, press the Enter key.
3
Push the DOWN arrow to change the type from Modbus-Slave to Modbus-Master, press
Enter to save the changes.
4
Connect the straight through male-female DB-9 serial cable from your laptop, or PC, to the
EIA-232 port on the LD5100.
5
Open the terminal emulation program (HyperTerminal) with a connection of 9600 Baud, 8
Data bits, Parity None, 1 Stop bit and Flow control set to off.
6
Press the Enter key on your laptop, or PC, to view the LD5100 Help menu.
7
Type “SC” to access the System Configuration menu (see Figure B.3).
Figure B.3
Configuration Menu from EIA-232 Connection
Summary of Contents for LD5100
Page 1: ...Leak Detection LD5100 User Guide...
Page 8: ...970 484 6510 8 rletech com Notes...
Page 11: ...970 484 6510 11 rletech com...
Page 12: ...970 484 6510 12 rletech com Notes...
Page 14: ...970 484 6510 14 rletech com Notes...
Page 24: ...www rletech com 24 970 484 6510 2 Connections and Settings Notes...
Page 30: ...www rletech com 30 970 484 6510 4 4 20mA Output Testing Notes...
Page 48: ...www rletech com 48 970 484 6510 7 EIA 232 Interface Notes...
Page 60: ...www rletech com 60 970 484 6510 A Updating Firmware Notes...
Page 66: ...www rletech com 66 970 484 6510 C Preventive Maintenance Notes...
Page 70: ...www rletech com 70 970 484 6510 D Troubleshooting Notes...